USER’S MANUAL
3KSS60400/50400
2
nd
Edition
Frequency Converter
Visicomm Industries LLC
4525 Sheridan Rd.
Racine WI 53403
Страница 1: ...USER S MANUAL 3KSS60400 50400 2nd Edition Frequency Converter Visicomm Industries LLC 4525 Sheridan Rd Racine WI 53403 ...
Страница 2: ...This Converter is designed with the following unique features l Double Conversion IGBT module Single control board design eliminates adjustment and minimizes maintenance l LCD display for unit status user friendly design l Special overload capacity design 150 overload for 30 sec l Built in isolation transformer to ensure total isolation between the input and output l Special airflow control to avo...
Страница 3: ...e converter is in fault condition 7 LCD DISPLAY 1 INPUT VOLTAGE 3 INPUT FREQUENCY 2 OUTPUT VOLTAGE 4 OUTPUT FREQUENCY 5 OUTPUT POWER 6 NO OUTPUT 8 LCD Switch Display items can be changed using the LCD switch 9 PUSH ON OFF SWITCH This switch turns the converter on or off 10 VENTILATION LOUVERS Please keep the ventilation louvers clean 3KSS60400 50400 FREQUENCY CONVERTER FRONT ...
Страница 4: ...er SWA Controls the AC Commercial input Power in addition This breaker trips If the output power Is subject to a Dead short 14 Input terminal The input power leads will be connected to the terminal block either 120VAC range or 220VAC range See spec sheet 15 output terminal 120V L N 16 output Voltage adjustment potentiometer 17 Ground terminal 3KSS60400 50400 FREQUENCY CONVERTER BACK ...
Страница 5: ... including the system neutral The Converter is shipped with these OUTPUT connections electrically isolated If a digital voltmeter is connected between any one of these OUTPUT terminals and the Earth Ground a significant voltage reading will be obtained This voltage is due to a small leakage current and is not considered a problem since only 1 or 2 ma is involved Output Isolation Many applications ...
Страница 6: ...s A SINGLE PHASE 220V INPUT This connection is usually used in 50Hz countries where a neutral is normally available B SPLIT PHASE 220V INPUT This connection is usually used in 60Hz countries where a 220V line is not normally available and where the input amperage makes using 120V inconvenient C SINGLE PHASE 120V INPUT D THREE PHASE 120 208 VAC USING LINE TO LINE INPUT To be used if the 120V line t...
Страница 7: ...to the input frequency CAUTION The output is floating and is electrically isolated from the input It is necessary to connect the output using one of the following three methods Note that these output voltages are widely adjustable using the voltage adjust rheostat A SINGLE PHASE 120V OUTPUT ...
Страница 8: ...oad Capacity 110 continuous 110 150 load 30 seconds over 150 causes unit to shut down Auto restart upon removal of overload Short Circuit Unit will cut out and must be manually restarted EMI Filter 10 100KHz at 40dB 100KHz 100MHz at 70dB Protection Over Temperature Inverter auto cut off when heat sink temp over 80ºC Overload Sounds continuously Audible Alarm Converter Fault Sounds continuously LCD...