Manual VIPA HMI 

Chapter 3   Installation Guidelines 

HB160E - TP - RE_62F-FCB0

 

- Rev. 11/14 

 

3-11 

Special precautions providing high noise immunity 

 

Inductors controlled by your programmable controller (e.g. contactors and 
relays) do not normally require additional snubber networks or suppressors 
as the respective modules have been provided with the required 
components. 
 
Snubber networks must only be connected to inductors when output 
circuits can be disabled by means of additional contacts (e.g. relay 
contacts). In this case the integrated suppressors on the module are also 
disabled. 
You can connect diodes to suppress back-emc, varistors or RC-networks 
to the inductors. 
 
Connections of  
DC-activated inductors 

Connections of  
AC-activated inductors 

using a diode 

using a Z-diode  using a varistor  using RC-network 

 

-

+

+

-

 

 
Every cubicle must be provided with a power outlet for the PU. These 
outlets must be wired to the distribution system, which is also used to 
connect the neutral conductor for the cubicle. 
 
The cubicle illumination should consist of incandescent lights, e.g. 
LINESTRA-lamps. Avoid using fluorescent lamps as these lamps can 
cause interference. 
If you can not avoid using fluorescent lamps you should implement the 
steps outlined in the following figure. 
 

 [1] 

Fluorescent 

lamp 

 

 

[2]  Screen above the lamp 

 

 [3] 

Screened 

cable 

 

 

[4]  Switch with metallic cover 

 

1

3

4

5

2

 

[5]  Line filter or screened power 

cable 

 

Inductors require

 

snubber networks 

Equipotential 
bonding 

Power outlet for 
PGs 

Cubicle 
illumination 

Suppression of 
fluorescent lamps 
in cubicles 

Содержание TP 605CQ

Страница 1: ...VIPA HMI Touch Panel 62F FCB0 Manual HB160E_TP RE_62F FCB0 Rev 11 14 April 2011...

Страница 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...

Страница 3: ...Installation 2 2 Commissioning 2 4 Connection to a PLC system 2 12 Operating system Windows CE 5 0 2 13 Communication via ActiveSync 2 19 Integrated Server 2 21 Access to the network resources 2 28 Fi...

Страница 4: ...Contents Manual VIPA HMI ii HB160E TP RE_62F FCB0 Rev 11 14...

Страница 5: ...or the installation The chapter closes with the technical data Chapter 2 Deployment Touch Panel This chapter deals with the application of the Touch Panel At the beginning of the chapter you get infor...

Страница 6: ...the topics for every chapter The manual is available in printed form on paper in electronic form as PDF file Adobe Acrobat Reader Button Buttons are put in brackets e g NEXT or OK Key Key entry are p...

Страница 7: ...nvironments EX zone The manual must be available to all personnel in the project design department installation department commissioning operation The following conditions must be met before using or...

Страница 8: ...Safety information Manual VIPA HMI 4 HB160E TP RE_62F FCB0 Rev 11 14...

Страница 9: ...TP 605CQ from VIPA Besides of a description of the single components of the Touch Panel you will also find the dimensions that are required for the installation The chapter closes with the technical...

Страница 10: ...eby causing the module to become inoperable or unusable Modules that have been damaged by electrostatic discharges may fail after a temperature change mechanical shock or changes in the electrical loa...

Страница 11: ...le for monitoring and controlling of process cycles Windows CE 5 0 Core Different HMI SCADA Runtime selectable 520MHz pulse frequency Work memory 64Mbyte about 6Mbyte memory for user data on board CF...

Страница 12: ...ture 1 Slot for storage medium CF SD MMC 2 Connection for interfaces and power supply T o u c h P a n e l 1 2 3 3 Display with touch sensitive area touch screen 1 Compact Flash 2 MMC SD 1 2 Note Pleas...

Страница 13: ...ce COM 1 3 MPI PROFIBUS DP RS485 interface 4 Host USB A interface 5 Slave USB B interface 6 RJ45 jack for Ethernet communication 7 Slot for DC 24V voltage supply 8 Slot for CF SD MMC storage medium No...

Страница 14: ...vice Slot for CF Here you may plug a CompactFlash type II The card may be plugged and removed during runtime and is immediately listed as Storage Card at My Device Every CompactFlash storage module ha...

Страница 15: ...8 TxD Line B 5 4 3 2 1 9 8 7 6 9 RxD Line B TxD A TxD B RxD A RxD B Shield RS422 Periphery 3 8 4 9 M5V TxD TxD RxD RxD P5V 5 6 Serial bus connection in 2 wire technology using half duplex mode Connec...

Страница 16: ...r rate up to 115 2kBaud Connection RS232 9pin plug Connection RS232 Pin RS232 1 CD 2 RxD 3 TxD 4 DTR 5 GND 6 DSR 7 RTS 8 CTS 1 2 3 4 5 6 7 8 9 9 RI RxD TxD GND TxD RxD 3 2 GND 5 RTS CTS 7 8 Shield RS2...

Страница 17: ...t is as follows Slave USB B Pin Assignment 1 VCC 2 DM 3 DP 2 1 3 4 4 GND The USB A interface of your PC can be connected to the Slave USB B interface of your Touch Panel deploying the USB programming...

Страница 18: ...W x H 200 x 144mm Front panel W x H 212 x 156mm Display size W x H 115 2 x 86 4mm Back side W x H x D 198 x 142 x 37mm Installation depth 37mm Note The degrees of protection are only guaranteed when...

Страница 19: ...rating controls Touchscreen resistive Keyboard external via USB Mouse external via USB Interfaces MPI PROFIBUSDP RS485 isolated MPI PROFIBUSDP connector Sub D 9 pin female CAN CAN connector Serial COM...

Страница 20: ...er Protect type front side IP 65 Protect type back side IP 20 Dimensions Front panel 212 x 156 x 7 5 mm Rear panel 198 x 142 x 37 mm Installation cut out Width 200 mm Height 144 mm Minimum 2 5 mm Maxi...

Страница 21: ...mbly and the connection of the Touch Panel The main part of the chapter introduces Windows CE and the various communication options offered by the Touch Panel Topic Page Chapter 2 Deployment Touch Pan...

Страница 22: ...le For the installation into a operating tableau and control cabinet fronts the Touch Panel requires the following front plate cutting W H Touch Panel W x H in mm 62F FCB0 200 x 144 The fixing techniq...

Страница 23: ...se flexible wires without end case as well as stiff wires Fix the conductors to the CageClamps like this DC 24V 1 2 3 1 Round opening for wires 2 Locking orange for screwdriver 3 Test point for 2mm te...

Страница 24: ...les are permitted Signal cables must not be let within the same cable shaft as high voltage cables As soon as the Touch Panel is provided by power supply the Touch Panel starts with user area of the V...

Страница 25: ...tored The backed up files may be restored by Restore Here you get information about Touch Panel like operating system images runtime version and tools With this button you may return to the user area...

Страница 26: ...d at Settings are activated With disabling Run on Startup the Touch Panel starts with the Windows operating system The functions preset at Settings are ignored With enabling Enable User Interface the...

Страница 27: ...the user respectively administrator area Here new buttons may be configured and assigned with corresponding programs You may choose Normal for the user area or Advanced for the administrator area Wit...

Страница 28: ...sword is defined you were prompted to enter the password If there is no password defined the administrator area is opened On delivery there is no password preset If you have forgot you password by ena...

Страница 29: ...are added by With the corresponding file is removed from the list With the file may be downloaded With Autostart a program from the program list can be selected which is to be started delayed For thi...

Страница 30: ...face on the Touch Panel start via the button Control Panel the tool Com2 Configuration In the opened dialog window you activate the RS485 or the RS422 interface Default off To remain the settings perm...

Страница 31: ...f not communicate via Movicon or zenon Via mode the interface could be set up on DP Slave Note It is possible to set up the DP slave with the tool via software but the hardware of the Touch Panel does...

Страница 32: ...runtime version of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via MPI field...

Страница 33: ...t Windows CE is a 32bit open and scalable platform for a multiplicity of communication and data processing devices The functions like multi tasking and multi threading are supported by this operating...

Страница 34: ...on an object open res executes this Drag By tapping on an object and then dragging you may move the object on the screen If no object is selected a frame is created by the dragging that selects the to...

Страница 35: ...ers you access to all components of your Touch Panel like e g applications system settings file browser etc 2 Open applications For every open application a button is to be found in the task bar There...

Страница 36: ...lusively entered via the software keyboard Keyboard Normal At pushed SHIFT key Meaning Home Position 1 End End BS Backspace up dn lt rt pgup Page pgdn Page ins Insert del Delete Tab Tabulator Shift Ca...

Страница 37: ...egister Double Tap you may use the grid pattern to preset a double click velocity and test this on the symbol below OK takes over the set value The calibration of the touch screens happens via the reg...

Страница 38: ...r the Touch Panel Baud Rate Enter here the transfer velocity of your MPI net The baud rate has to be identical for every MPI participant within the network According to the Baud Rate the network param...

Страница 39: ...data transfer Before you may access the Touch Panel from the PC via ActiveSync you have to install it on the PC ActiveSync is freeware and may be downloaded from www microsoft de Download the ActiveSy...

Страница 40: ...Touch Panel is recognized and the dialog window new partnership opens Choose yes for fixing a partnership and push Next In the now opening window de activate all synchronization settings and click on...

Страница 41: ...ia START Programs KuK Tools before switching off Per default the following server are integrated ftp server activated http server activated Telnet activated VNC not activated Phrases that are used in...

Страница 42: ...ftp connection If there are still problems with the ftp access please ask your system administrator ftp access possible with version 5 5 or higher use passive ftp mode activate directory view for ftp...

Страница 43: ...your Touch Panel with the network where your PC is a member via an Ethernet cable Switch on your Touch Panel As soon as your Touch Panel is connected via Ethernet you may monitor the IP address data v...

Страница 44: ...o the address bar IP address webadmin Enter the following into the authentification User name wince Password vipatp Remember to store your changes permanently in the registry via Start Programs KuK_To...

Страница 45: ...ication is not possible The establishing of a Telnet connection is password protected and has the following approach Start a Telnet client like for example MS DOS console at your PC and enter the foll...

Страница 46: ...FCB0 Rev 11 14 After establishment of a Telnet connection the Touch Panel provides you with commands A list of possible commands with a short description is available via the command help By beginnin...

Страница 47: ...proach Click on and open the Windows directory You have to deactivate every option at View Options to show the VNC server file Start the VNC server by executing the file winvnc exe To show the server...

Страница 48: ...server To test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection of a local name at the Touch Pane...

Страница 49: ...twork printer For example you may print the content of the current directory using dir network printer The listing command for all network connections of your Touch Panel is net use You may terminate...

Страница 50: ...and approved by VIPA GmbH Go to www vipa de Click at Service Support Downloads Firmware and navigate via HMI to the firmware for your Touch Panel Transfer the os file to your PC Copy the file to your...

Страница 51: ...Here we describe possible paths how interference can enter the controller how you ensure the electromagnetic compatibility EMC and how to approach shielding and screening issues Topic Page Chapter 3...

Страница 52: ...industrial environments and complies with EMC requirements to a large degree In spite of this you should implement an EMC strategy before installing any components which should include any possible so...

Страница 53: ...te to the temporal change of the voltage Interference through parallel signal lines Static discharge of the personnel Contactors Inductive coupling Automation System Disruptor inductive coupling line...

Страница 54: ...roups High voltage lines power supply lines signal lines data lines Always install high voltage lines and signal or data lines in separate channels or bundles Install signal and data lines as close as...

Страница 55: ...cent lamps Create a single reference potential and ensure that all electrical equipment is grounded wherever possible Ensure that grounding measures are implemented effectively The controllers are ear...

Страница 56: ...t may only get voltage in case of an error The ground must not adopt dangerous contact voltage even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid...

Страница 57: ...to divide the cables in different groups and install each group itself Group A screened bus and data lines screened analog lines unshielded lines for direct voltage 60V unshielded lines for alternatin...

Страница 58: ...be installed on metallic cable trays A galvanic connection must be provided for joints between cable trays You must abide by the applicable lightning protection and grounding regulations when installi...

Страница 59: ...m 2 Cu for equipotential bonding conductors up to 200m 25mm2 Cu for equipotential bonding conductors exceeding 200m Use copper or galvanized steel for equipotential bonding conductors These must be co...

Страница 60: ...recommended that the remove the insulation from the screened cable without cutting the screen and to attach this point to the screening neutral rail Note Potential differences can give rise to an equ...

Страница 61: ...ections of DC activated inductors Connections of AC activated inductors using a diode using a Z diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU Th...

Страница 62: ...l contact washer Have the connection been protected from corrosion e g by means of grease Have doors been grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabli...