![VIPA System 200V IM Series Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/vipa/system-200v-im-series/system-200v-im-series_manual_1029241073.webp)
Manual VIPA System 200V
Chapter 3 Profibus DP
HB97E - IM - Rev. 06/29
3-41
IM 253-2DP50 - DP-V0 slave (redundant) - Structure
In principal, the IM 253DPR consists of 2 Profibus DP slave connections.
The two Profibus slaves are controlling the operating modes of each other.
Both slaves have the same address at the Profibus and are communicating
with a redundant DP master.
Both slaves are reading the peripheral inputs. Only one slave at a time has
access to the peripheral outputs. The other slave is passive and in stand-
by. As soon as the active slave is failing, the passive slave accesses the
peripheral outputs.
I/O
1.Slave 2.Slave
CPU
IM 208
1.Master 2.Master
I/O
I/O
IM 253 DPR
IM 253 DPR
1.Slave 2.Slave
Next DPR-Slave
Please regard to use a redundant DP master for the redundant deployment
of the slave module. Every master unit needs the same parameterization
and bus configuration.
•
2 redundant channels
•
DPR slave for max. 32 peripheral modules (max. 16 analog modules)
•
Max. 152Byte input data and 152Byte output data
•
Internal diagnostic protocol with a time stamp
•
Integrated DC 24V power supply for the peripheral modules (max. 3.5A )
•
Supports all Profibus data transfer rates
Redundant system
Requirements for
the deployment
Properties
IM 253DPR
Содержание System 200V IM Series
Страница 1: ...Manual VIPA System 200V IM Order No VIPA HB97E_IM Rev 06 29...
Страница 2: ...Lerrzeichen...
Страница 6: ...About this manual Manual VIPA System 200V Subject to change to cater for technical progress...
Страница 10: ...Contents Manual VIPA System 200V iv HB97E IM Rev 06 29...
Страница 18: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E IM Rev 06 29...
Страница 136: ...Chapter 3 Profibus DP Manual VIPA System 200V 3 104 HB97E IM Rev 06 29...
Страница 338: ...Chapter 8 Ethernet coupler Manual VIPA System 200V 8 34 HB97E IM Rev 06 29...
Страница 344: ...Chapter 9 Bus expansion modules IM 260 IM 261 Manual VIPA System 200V 9 6 HB97E IM Rev 06 29...