VIPA Accessories
ProfiHub B5 | 973-5BE00 | Manual
HB151E | Rev. 11/38
September 2011
Страница 1: ...VIPA Accessories ProfiHub B5 973 5BE00 Manual HB151E Rev 11 38 September 2011...
Страница 2: ...c Compatibility Directive 2006 95 EC Low Voltage Directive Conformity is indicated by the CE marking affixed to the product Conformity Information For more information regarding CE marking and Declara...
Страница 3: ...ed without warranties The information is subject to change without notice Important passages in the text are highlighted by following icons and headings Danger Immediate or likely danger Personal inju...
Страница 4: ...ighly integrated components in MOS Technology These components are extremely sensitive to over voltages that can occur during electrostatic discharges The following symbol is attached to modules that...
Страница 5: ...ved message on one channel and transfers it to all the other channels Because the ProfiHub B5 creates isolated segments the devices can now be removed and added during operation Also electrical bus pr...
Страница 6: ...erial placement or cascading of ProfiHubs No PROFIBUS address required Integrated termination facilities switches Configurable grounding system direct or capacitive IP 20 classification nach DIN 40 05...
Страница 7: ...e installations Every channel is electrically isolated and internally connected to the transparent intelligent backbone The termination is switchable and powered by the ProfiHub The shielding of the P...
Страница 8: ...If by accident on 1 channel the Direct Grounding is connected with the Indirect Grounding the Direct Grounding wins The cables on the channels and the Main Channel should comply with the PROFIBUS DP...
Страница 9: ...ommunicating on the Main Channel No problem has been detected Problem in the cabling has been detected Main Channel Main ERROR red Problem in the cabling has been detected Main Channel Termination off...
Страница 10: ...d on the bottom left of the ProfiHub B5 PIN Wiring I Indirect grounding The power supply has to comply with the following specifications Voltage DC 10 32V Current Min 130mA Wire diameter 2 5mm To conn...
Страница 11: ...Out cable to the right connector of the Main Channel The second method is to place a PROFIBUS standardized plug with an in out cable on the DB9 connector DB9 Bus In Out Connector Communication status...
Страница 12: ...ic channel Communication status LED Channel 1 Channel connector Channel 1 Channel connector Channel 1 Pin Clamp Wiring A green wire B red wire Cable shielding or I Cable shielding Note Connecting the...
Страница 13: ...e channels have been set to ON by default Because it is assumed that the new segment is started at the ProfiHub Termination Main Channel Termination LED Main Channel The termination LED of the specifi...
Страница 14: ...locked to a certain transmission speed the baudrate switch should be set to the required value Settings Values 0 Auto detect Default 1 9 6kbps 2 19 2kbps 3 45 45kbps 4 93 75kbps 5 187 5kbps 6 500kbps...
Страница 15: ...1 25Tbit at 9 6kbps to 93 75kbps 1 3Tbit at 187 5kbps to 500kbps 1 4Tbit at 1 5Mbps 1 6Tbit at 3Mbps 2 0Tbit at 6Mbps 3 0Tbit at 12Mbps Delay time jitter Max 1 4 bit time Specification PROFIBUS cable...
Страница 16: ...sories 14 HB151D Rev 11 38 Reverse polarity protection Yes Cable thickness 10mm when the ground rail is used Wire diameter 2 5mm2 Others MTBF 398723 hours based on IEC62380 RDF 2000 UTE C 80 810 mathe...