Chapter 3 Deployment CPU 21x-1Bx06
Manual VIPA System 200V
3-20
HB97E - CPU - RE_21x-1Bx06 - Rev. 13/20
Overall reset
During the overall reset the entire user memory is erased. Data located in
the memory card is not affected.
You have 2 options to initiate an overall reset:
•
initiate the overall reset by means of the function selector switch
•
initiate the overall reset by means of the configuration software e.g.
Siemens SIMATIC manager
Note!
You should always issue an overall reset to your CPU before loading an
application program into your CPU to ensure that all blocks have been
cleared from the CPU.
Condition
The operating mode of the CPU is STOP. Place the function selector on the
CPU in position "ST"
→
the S-LED is on.
Overall reset
•
Place the function selector in the position MR and hold it in this position
for app. 3 seconds.
→
The S-LED changes from blinking to permanently
on.
•
Place the function selector in the position ST and switch it to MR and
quickly back to ST within a period of less than 3 seconds.
→
The S-LED blinks (overall reset procedure).
•
The overall reset has been completed when the S-LED is on
permanently.
→
The S-LED is on.
The following figure illustrates the above procedure:
R
S
PW
SF
R
S
PW
SF
R
S
PW
SF
R
S
PW
SF
1
2
3
4
3 Sec.
3 Sec.
RN
ST
MR
RN
ST
MR
RN
ST
MR
RN
ST
MR
Overview
Overall reset by
means of the
function selector
Содержание CPU 214
Страница 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 1Bx06 Rev 13 20 May 2013...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 1Bx06 Rev 13 20...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 1Bx03 Rev 13 20...
Страница 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E CPU RE_21x 1Bx06 Rev 13 20...