Chapter 4 Deployment CP 343-2P ASI
Manual VIPA System 300V
4-20
HB130E - CP - RE_343-2AH10 - Rev. 08/41
Firmware update
By means of a MMC and exclusive with a SPEED7-CPU 31xS from VIPA
there is the opportunity to execute a firmware update at the CP. For this an
accordingly prepared MMC must be in the CPU during the start-up. As
soon as the firmware is more current than in the CP, the CP gets the new
firmware.
So a firmware files may be recognized and assigned with start-up, a pkg
file name is reserved for each updatable component and hardware release,
which begins with "px" and differs in a number with six digits. With the CP
343-2P ASI the name of the pgk file may be found at lable on the backside
of the module. Information about the CP firmware may also be found at the
web page of the SPEED7 CPU. Here among others each updateable
component at the standard bus is listed. More may be found at the manual
of the SPEED7 CPU at "Access to the internal web page".
Note!
Please regard for a CP firmware update a SPEED7 CPU firmware version
starting with V340 is necessary!
The latest 2 firmware versions may be found in the service area at
www.vipa.de.
For example the following file is necessary for the firmware update of the
CP 343-2P ASI with hardware release 1: Px000084_Vxxx.zip
Attention!
When installing a new firmware you have to be extremely careful. Under
certain circumstances you may destroy the CPU respectively the CP, for
example if the voltage supply is interrupted during transfer or if the
firmware file is defective.
In this case, please call the VIPA-Hotline!
Please regard that the version of the update firmware has to be different
from the existing firmware otherwise no update is executed.
More information to the proceeding with a firmware update may be found at
the manual of the SPEED7 CPU at "Firmware update".
Overview
Latest Firmware at
www.vipa.de
Execute firmware
update