Manual VIPA System 200V
Chapter 4 CP 240 - serial
HB97E - CP - Rev. 11/30
4-39
Modbus - Error messages
At the communication at Modbus there are 2 error types:
•
Master doesn’t receive valid data
•
Slave responds with error message
If the slave doesn’t answer within the specified delay time or if a telegram is
defective, the master enters an error message into the receive block in
plain text.
The following error messages may occur:
ERROR01 NO DATA
Error no data
No telegram arrived within the specified delay
time.
ERROR02 D LOST
Error data lost
No data is available because either the receive
buffer is full or an error occurred in the receive
section.
ERROR03 F OVERF
Error frame overflow
The telegram end wasn’t recognized or maximum
telegram length exceeded.
ERROR04 F INCOM
Error frame incomplete
Only a part telegram has been received.
ERROR05 F FAULT
Error frame Fault
The check sum of the telegram is faulty.
ERROR06 F START
Error frame start
The start bit it wrong. this error may only occur
with Modbus-ASCII.
If the slave answers with an error, the function code is sent back like shown
below, marked as “or” with 80h:
DB11.DBD 0
DW#16#05900000
with 05
→
90
→
0000
→
Respond telegram
Slave address 05h
Function code 90h (error message, for 10h
OR 80h = 90h)
The rest data is not relevant, for an error
has been sent.
Overview
Master doesn’t
receive valid data
Slave answers
with error
message
Содержание CP 240 RS232
Страница 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Страница 2: ...L...
Страница 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Страница 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Страница 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Страница 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...