Chapter 5 Deployment I/O periphery
Manual VIPA System 300S SPEED7
5-18
HB140E - CPU SC - RE_313-6CF03 - Rev. 07/45
Counter - Functions
•
Start the Siemens SIMATIC Manager with your project and open the
hardware configurator.
•
Place a profile rail.
•
Configure at slot 2 the corresponding CPU from Siemens CPU 31xC.
•
Open the dialog window "Properties" by a double click to the
Count
submodule of the CPU.
•
As soon as an operating mode to the corresponding channel is selected,
a dialog window for this operating mode is created and displayed and
filled with default parameters.
•
Execute the wished parameterization.
•
Store the project with
Station
>
Save and compile
.
•
Transfer the project to the CPU.
Via the parameterization you have the opportunity to define a main
counting direction for every counter. If "none" or "endless" is chosen, the
complete counting range is available:
Limit counter
Valid value range
Lower count limit
-2 147 483 648 (-2
31
)
Upper count limit
+2 147 483 647 (2
31
-1)
Otherwise this range may be limited in both directions by a start value as
load value
and an
end value
.
Main counting direction forward
Upper restriction of the count range. The counter counts 0 res. load value
in positive direction until the parameterized end value –1 and jumps then
back to the load value with the next following encoder pulse.
Please note a load value may exclusively be set by the request interface of
the counter.
Main counting direction backwards
Lower restriction of the count range. The counter counts from the
parameterized start- res. load value in negative direction to the
parameterized end value +1 and jumps then back to the start value with the
next following encoder pulse.
Please note an end value may exclusively be set by the request interface
of the counter.
Parameterization
Load value,
End value
Main counting
direction
Содержание 313-6CF03
Страница 2: ...Lerrzeichen ...
Страница 40: ...Chapter 3 Hardware description Manual VIPA System 300S SPEED7 3 14 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...
Страница 122: ...Chapter 5 Deployment I O periphery Manual VIPA System 300S SPEED7 5 36 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...
Страница 140: ...Chapter 6 Deployment PtP communication Manual VIPA System 300S SPEED7 6 18 HB140E CPU SC RE_313 6CF03 Rev 07 45 ...