Analog value representation
As soon as a measuring value exceeds the overdrive res. underdrive
range, the following value is returned:
Measuring value > Overdrive range:
32767 (7FFFh)
Measuring value < Underdrive range:
-32768 (8000h)
At parameterization error or de-activated analog part the measuring value
32767 (7FFFh) is returned. When leaving the defined range during analog
output 0V respectively 0A is issued.
In the following all measuring ranges are specified, which are supported by
the analog part. With the formulas it may be converted between measuring
and analog value.
The analog values are represented in two’s complement format.
Analog value
High-Byte
Low-Byte
Bit
number 15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
11 Bit + sign
SG Relevant output value
X* X X X
* The lowest value irrelevant bits of the output value are marked with "X".
Bit 15 serves as algebraic sign bit. Here is:
Bit 15 = "0"
→
positive value
Bit 15 = "1"
→
negative value
General
Numeric notation
in Siemens
S7 format
Algebraic
sign bit (SG)
Содержание 134-4E Series
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA System 100V ii HB100E EM RE_134 4Ex Rev 08 23...
Страница 18: ...Chapter 1 Basics Manual VIPA System 100V 1 10 HB100E EM RE_134 4Ex Rev 08 23...
Страница 44: ...Chapter 2 Hardware description and deployment Manual VIPA System 100V 2 26 HB100E EM RE_134 4Ex Rev 08 23...
Страница 46: ...Index Manual VIPA System 100V A 2 HB100E EM RE_134 4Ex Rev 08 23 M Stich...