Vimar Eikon Evo 21296 Скачать руководство пользователя страница 1

Viale Vicenza, 14 - 36063 Marostica VI - Italy 

Tel. +39 0424 488 600 - Fax (Italia) +39 0424 488 188 

Fax (Export) +39 0424 488 709

www.vimar.com

CLASS  A  GFCI  20A  125V

125V  15A RECEPT

60HZ

PA

T.PEND.

TESTTEST

RESETRESET

LINE

GRN

LOAD

HOT

WHITE

Receptacle
Outlet

Mounting

bracket

Grounding terminal (Green):
Connection for bare copper 
or green wire

LINE

White terminal 
(Silver): 
Connection for 
LINE cable’s 
white wires

LOAD

White terminal 
(Silver): 
Connection for 
LOAD cable’s 
white wires

Screw (terminal) colors:
Green = Grounding terminal
Silver = White terminals
Brass = Hot terminals

LINE

Hot terminal (Brass): 
Connection for the LINE 
cable’s black wire

LOAD

Hot terminal (Brass): 
Connection for the LINE 
cable’s black wire

A yellow sticker covers 
the LOAD terminals.
Do not remove the 
sticker at this time

TEST button:

See “Procedure”

RESET button:

See “Procedure”

Trip

indicator light

49400555B0  02  1601

VIMAR - Marostica - Italy

Double 2P+E 15A 125 V~ 60 Hz socket outlet, American standard, with ground fault circuit interrupter (GFCI) and built-in mounting frame, to 
complete with 3-module cover plate.

DESCRIPTION.

A GFCI receptacle is different from conventional receptacles. In the event of a ground 
fault, a GFCI will trip and quickly stop the flow of electricity to prevent serious injury.

CHARACTERISTICS.

• Rated voltage 125 V~ 60 Hz.
• Rated current corresponding to the socket outlet standard 15 A.
• GFCI Class A (trip 6 mA or more).

ATTENTION:

 

If you install the device in the Eikon Evo cover plate, 
make sure to remove the side lugs as shown in the 
picture beside.

Definition of a ground fault:

Instead of following its normal safe path, electricity passes through a person’s body 
to reach the ground. For example, a defective appliance can cause a ground fault. A 
GFCI receptacle does not protect against circuit overloads, short circuits, or shocks. 
For example, you can still be shocked if you touch bare wires while standing on a 
non-conducting surface, such as a wood floor.

TEST YOUR WORK. 
Why perform this test?

• If you miswired the GFCI, it may not prevent personal injury or death due to a 

ground fault. (electrical shock).

• If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will still 

operate like an ordinary receptacle, but it will not interrupt a ground fault.

TESTTEST

RESETRESET

TESTTEST

RESETRESET

TESTTEST

RESETRESET

Procedure:

(a) This GFCI is shipped from the factory in the trip-

ped condition and can not be reset until it is wired 
correctly and power is supplied to the device. 
Plug a lamp or radio into the GFCI (and leave it 
plugged in). Turn the power ON at the service 
panel. Press the RESET button fully, make sure 
the lamp or radio is ON. If the lamp or radio is still 
OFF or the RESET button can not be engaged, 
go to the Troubleshooting section because LINE 
and LOAD wiring connection have been reversed.

(b) Press the TEST button fully, the GFCI will trip 

and the lamp or radio will be OFF. To restore 
power, press the RESET button.

(c) If you installed your GFCI using CONNECTION 

B, plug a lamp or radio into surrounding 
receptacles to see which one(s), in addition to 
the GFCI, lost power when you pressed the 
TEST button. Do Not plug life saving devices 
into any of the receptacles that lost power. 
Place a “GFCI Protected” sticker on every 
receptacle that lost power. Then press the 
RESET button to reset the GFCI.

(d) Press the TEST button (then RESET button) 

every month to assure proper operation. If the 
GFCI can not be reset, then it must be replaced.

(e) If the GFCI consistently trips it indicates end of 

life and GFCI must be replaced.

TROUBLESHOOTING.

Turn the power OFF and check the wire connections against the appropriate wiring 
diagram in step CONNECTION A or CONNECTION B. Make sure that there are no loose 
wires or loose connections. Also, it is possible that you reversed the LINE and LOAD 
connections. LINE/LOAD reversal will be indicated by power remaining ON at the GFCI 
after you press the GFCI’s TEST button. Reverse the LINE and LOAD connections if 
necessary. Start the test from the beginning if you rewired any connections to the GFCI.

CAUTION.

To prevent severe shock or electrocution always turn the power OFF at the service 
panel before working with wiring.

PLACEMENT IN CIRCUIT:

The GFCI’s place in the circuit determines if it protects other receptacles in the circuit.

Placing the GFCI in position A will also provide protection to “load side” receptacles B and C. On the other 
hand, placing the GFCI in position C will not provide protection to receptacles A or B. Remember that 
receptacles A, B and C can be in different rooms.

FRONT VIEW

BACK VIEW

LINE

GRN

LOAD

HOT

WHITE

LINE cable brings

power to the GFCI

Mounting box

LOAD cable feeds power 
to other receptacle(s)

Grounding 
connection to box
(if box has a 
grounding terminal)

Wire connector

Yellow sticker remain 
in place to cover the 
LOAD terminals

LINE

GRN

LOAD

HOT

WHITE

ATTENTION

LINE cable brings

power to the GFCI

Wire connector

Mounting box

Grounding 
connection to box
(if box has a 
grounding terminal)

CONNECTION B.

CONNECTION A.

TESTTEST

RESETRESET

LINE

LOAD

LINE

LOAD

A

LINE

B

C

Service

Panel

SAMPLE CIRCUIT:

Eikon Evo

21296

Idea

16296

Plana

14296

Arké

19296

• Use this GFCI receptacle with copper or copper-clad wire. Do not use it with aluminum wire.
• Do not install this GFCI receptacle on a circuit that powers life support equipment because if the GFCI 

trips it will shut down the equipment.

  Must be installed by a skilled person in accordance with national and local electrical codes

.

21653

EIKON

EVO

MADE

IN

ITAL

Y

Отзывы: