Day light saving time “By date” [Time parameters]
7.2
Analog measurements [Analog inputs]
Data logger performed functions:
•
Analog signal (current) measurement,
•
Filtering,
•
Conversion into physical parameter value (Current value),
•
Storing Data (average value during a set period),
•
Alarming in case of deviation,
•
Calibration.
7.2.1
Configuration
Parameters:
•
Channel usage,
•
Current range,
•
Filter averaging duration,
•
Conversion into physical parameter range (“Min. value” and “Max. value”) ,
•
Alarm filter time,
•
Alarm limits (upper and lower),
•
Alarm case (Out of range, Out & return to range).
Data logger periodically (analog measurement perod 0.1 seconds) measures current of all Analog
channels and converts to physical value. User can chose from three (0-20mA, 4-20mA and 0-
5mA, with accuracy 0,005mA) measurement ranges (see
From current, using “Min. value” (float) and “Max. value” (float) range (formula:
) is
recalculated physical value.
Measured values can be filtered. For filtration is used liner filter – calculated average value of
Содержание MX-7
Страница 1: ...2 ...
Страница 4: ...5 9 6 USB cable 85 9 7 Installing VILTRUS USB driver 85 9 8 TCP IP settings 87 ...
Страница 22: ...23 see Pic 6 3 6 V 5 V 6V 8 V 10 V Pic 6 Power for external device DIP switch ...
Страница 53: ...54 Pic 48 Routing configuration example ...
Страница 54: ...55 Pic 49 Routing screenshots ...
Страница 59: ...60 2 Set COM port number UART port must be configured and assigned to COM client on ...
Страница 66: ...67 Pic 61 Setting up RAY 1 as External module by example ...
Страница 75: ...76 Pic 71 Records in archives section Archives Configutation ...