Quadra-fire  •  QV32B, QV36B  •  2013-900  Rev. F  •  9/06

Models:

QV32B
QV36B

Installers Guide

Underwriters

Laboratories Listed

- Do not store or  use gasoline or other flam-

mable vapors and liquids in the vicinity of this
or any other appliance.

-

What to do if you smell gas

• Do not try to light any appliance.

• Do not touch any electrical switch.

• Do not use any phone in your building.

• Immediately call your gas supplier from a

neighbor's phone. Follow the gas supplier's
instructions.

• If you cannot reach your gas supplier, call

the fire department.

- Installation and service must be performed by a

qualified installer, service agency, or the gas
supplier.

WARNING: IMPROPER INSTALLA-
TION, ADJUSTMENT, ALTERATION,
SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAM-
AGE. REFER TO THIS MANUAL. FOR
ASSISTANCE OR ADDITIONAL INFOR-
MATION CONSULT A QUALIFIED IN-
STALLER, SERVICE AGENCY, OR THE
GAS SUPPLIER.

READ THIS MANUAL BEFORE INSTALLING OR
OPERATING THIS APPLIANCE. THIS INSTALLERS
GUIDE  
MUST BE LEFT WITH APPLIANCE FOR
FUTURE REFERENCE.

1. This appliance may be installed in an af-

termarket, permanently located, manufac-
tured (mobile) home, where not prohibited
by local codes.

2. This appliance is only for use with the type

of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases, unless a certified kit is used.

Please contact your Quadra-Fire dealer
with any questions or concerns. For the
number of your nearest Quadra-Fire
dealer, please visit www.quadrafire.com.

Printed in U.S.A.   Copyright 2006

WARNING: IF THE INFORMATION
IN THESE INSTRUCTIONS IS NOT
FOLLOWED EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUS-
ING PROPERTY DAMAGE, PER-
SONAL INJURY, OR DEATH.

Quadra-Fire, a brand of Hearth & Home Technologies
1445 North Highway, Colville, WA 99114

This product may be covered by one or more of the following patents: (United States) 4593510, 4686807, 4766876, 4793322, 4811534, 5000162, 5016609, 5076254, 5113843, 5191877, 5218953, 5263471,
5328356, 5341794, 5347983, 5429495, 5452708, 5542407, 5601073, 5613487, 5647340, 5688568, 5762062, 5775408, 5890485, 5931661, 5941237, 5947112, 5996575, 6006743, 6019099, 6048195, 6053165,
6145502, 6170481, 6237588, 6296474, 6374822, 6413079, 6439226, 6484712, 6543698, 6550687, 6601579, 6672860, 6688302B2, 6715724B2, 6729551, 6736133, 6748940, 6748942, 6769426, 6774802,
6796302, 6840261, 6848441, 6863064, 6866205, 6869278, 6875012, 6880275, 6908039, 6919884, D320652, D445174, D462436; (Canada) 1297749, 2195264, 2225408, 2313972; (Australia) 780250,
780403, 1418504 or other U.S. and foreign patents pending.

In the Commonwealth of Massachusetts:

• installation must be performed by a licensed

plumber or gas fitter;

See Table of Contents for location of additional
Commonwealth of Massachusetts requirements.

Содержание QV32B

Страница 1: ...pliance is not convertible for use with other gases unless a certified kit is used Please contact your Quadra Fire dealer with any questions or concerns For the number of your nearest Quadra Fire deal...

Страница 2: ...lace front READ and UNDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warr...

Страница 3: ...he Vent System 18 A Vent System Approvals 18 B Installing Vent Components 28 C Vent Termination 31 Step 4 Positioning Leveling and Securing the Fireplace 34 Step 5 The Gas Control Systems 34 Step 6 Th...

Страница 4: ...36B 2013 900 Rev F 9 06 Part number list on following page 5 4 2 1 3 6 Log Set Assembly 11 10 8 7 9 13 12 NG LP Exploded Parts Diagram Service Parts QV32B Beginning Manufacturing Date 6 03 Ending Manu...

Страница 5: ...LP Pre 10 06 Post 10 06 060 519 230 1520 Y Y Pilot Spud NG Pre 10 06 Post 10 06 446 505 2103 116 Y Y Pilot Spud LP Pre 10 06 Post 10 06 446 517 2103 117 Y Y ACCESSORIES Fan Kit GFK 160A Extended Vert...

Страница 6: ...QV36B 2013 900 Rev F 9 06 Part number list on following page 4 6 Log Set Assembly 1 11 10 8 7 9 5 2 3 12 NG LP Exploded Parts Diagram Service Parts QV36B Beginning Manufacturing Date 6 03 Ending Manuf...

Страница 7: ...RV485 301 N A Y Lava Rock Bag 060 721 Mineral Wool 050 721 Exhaust Restrictor 530 299 Glass Latch Assembly 386 122A Y Touch Up Paint TUP GBK 12 Regulator NG Pre 10 06 Post 10 06 060 518 230 1570 Y Y R...

Страница 8: ...Gas Connector 530 302A Y 4 Burner Plate Gasket 530 431 5 Burner Neck Gasket 2045 407 6 Pilot Assembly NG PRE 10 06 POST 10 06 530 510A 2103 010 Y Y 6 Pilot Assembly LP PRE 10 06 POST 10 06 530 511A 2...

Страница 9: ...sitting room in the U S A and Canada Appliance Certification The Village Collection fireplace models discussed in this Installers Guide have been tested to certification standards and listed by the a...

Страница 10: ...in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fuele...

Страница 11: ...ety and benefit Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Quadra Fire Warranty will be voided by and Hearth Home Technologies disclaims any...

Страница 12: ...CCESS TOP STANDOFFS GAS LINE ACCESS 5 1 16 129mm 2 3 16 55mm 34 5 8 879mm 30 3 4 781mm 15 3 8 391mm 15 7 8 403mm 36 1 8 917mm 40 7 8 1039mm 3 9 16 90mm ELECTRICAL ACCESS 37 7 8 961mm 8 203mm 6 5 8 168...

Страница 13: ...GAS ACCESS GAS CONTROLS ELECTRICAL ACCESS TOP STANDOFFS 25 3 4 653mm 12 7 8 326mm 15 7 8 402mm 8 13 16 223mm 16 3 8 414mm 31 1 8 790mm 2 3 16 55mm 5 1 16 129mm GAS LINE ACCESS 31 790mm 36 913mm 6 7 8...

Страница 14: ...g the Fireplace Chase A chase is a vertical box like structure built to enclose the gas fireplace and or its vent system Vertical vents that run on the outside of a building may be but are not require...

Страница 15: ...AILS BEFORE FRAMING Framing should be constructed of 2 X 4 lumber or heavier The framing headers may rest on the fireplace stand offs The center of the framing hole is one 1 inch 25 4mm above the cent...

Страница 16: ...S 34 93mm AT EACH JOINT Figure 6 DVP Series Direct Vent Component Specifications 5 inch inner pipe 8 inch outer pipe DVP90ST 12 9 16 11 1 4 7 1 4 1 1 4 TYP 1 2 TYP 8 9 16 DVP36 DVP48 48 24 36 4 6 DVP4...

Страница 17: ...pecifications 4 inch inner pipe 6 5 8 inch outer pipe 120 3048mm 24 610mm 36 914mm 60 1524mm 9 1 4 6 5 8 6 1 2 6 3 8 6 1 2 9 5 8 9 5 8 6 5 8 6 3 8 8 3 4 SL 09D 12 17 SL 12 17D SL12 17D SL 24D SL 36D S...

Страница 18: ...is Installers Guide Figure 8 shows vent system components and terminations The vent systems installed on this gas fireplace may in clude one two or three 90 elbow assemblies The rela tionships of vert...

Страница 19: ...d in any location where it is necessary to maintain the necessary clearance to combustibles A simple up and out installation Figure 9 requires only enough support to maintain the necessary clearance t...

Страница 20: ...V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 48m 5 FT 1 52m 16 FT 4 8m VENTING WITH ONE 1 90o ELBOW PROPANE H MAX 16...

Страница 21: ...X 1 86 m 12 MAX 3 6m 4 MIN 1 22 m 8 MAX 2 48 m 16 MAX 4 8m V H H1 40 MAX 12 4 m H 8 MAX 2 48 m H H1 16 MAX 4 8m Figure 14 Venting with Two 90 Elbows V FT H H1 FT 1 MIN 305 mm 2 MAX 610 mm 2 MIN 610 mm...

Страница 22: ...3mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32B V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT...

Страница 23: ...3mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32B V MIN H MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 914mm 6 FT 1 86m 4 FT 1 22m 8 FT 2 4...

Страница 24: ...MAX 3 72m 4 MIN 1 22m 8 MAX 2 48m 16 MAX 4 8m V1 V H H1 40 MAX 12 4m H 8 MAX 2 48m H H1 16 MAX 4 8m V H H H1 1 MIN 305 mm 2 MAX 610 mm 4 MAX 1 22m 2 MIN 610 mm 4 MAX 1 22 m 8 MAX 2 48m 3 MIN 914 mm 6...

Страница 25: ...FT 4 8m 16 FT 4 8m VENTING WITH THREE 3 90o ELBOWS NATURAL GAS V H V1 H1 MAX 40 FT 12 2m VENTING WITH THREE 3 90o ELBOWS PROPANE MODEL QV32B MODEL QV36B V MIN H MAX H H1 MAX H MAX H H1 MAX 90o Elbow o...

Страница 26: ...MODEL QV36B H H1 MAX 2 5 FT 863mm 3 FT 914mm 4 FT 1 22m 6 FT 1 86m 8 FT 2 48m 16 FT 4 8m MODEL QV32B V MIN H H1 MAX 90o Elbow on Top 2 5 FT 863mm 1 FT 305mm 2 5 FT 863mm 2 FT 610mm 4 FT 1 22m 3 FT 91...

Страница 27: ...WITH FOUR 4 90 ELBOWS NATURAL AND PROPANE GAS V MIN H MAX 2 609mm 5 1 52m V1 MIN H1 MAX V2 MIN 5 1 52m 5 1 52m 4 5 1 37m V V1 V2 H H1 MAX 40 12 2m V H V2 V1 H1 NOTE There MUST be a 25 reduction in to...

Страница 28: ...COLLARS YOU ARE USING COULD NEGATIVELY AFFECT FIREPLACE PERFORMANCE WARNING YOU MUST LEAVE THE INSULA TION IN PLACE IN THE SET OF COLLARS YOU ARE NOT USING FAILURE TO DO THIS COULD CAUSE A FIRE DVP Se...

Страница 29: ...alpipesupport To install support brackets for horizontal runs Place the pipe supports around the vent pipe Nail the pipe supports to the framing members WALL BRACKET WALL STUD 1 INCH MIN 25 4mm 8 FT 2...

Страница 30: ...10 254mm 10 254mm Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the firestops MUST BE placed to wards the top of t...

Страница 31: ...ructions Figure 29 Trapezoid Termination Cap 7 1 4 184mm WARNING THE TERMINATION CAP MUST BE POSITIONED SO THAT THE ARROW IS POINTING UP WARNING VENTING TERMINALS SHALL NOT BE RECESSED INTO A WALL OR...

Страница 32: ...spaces open only on one side and with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All m...

Страница 33: ...AM FOR MINIMUM HEIGHTS PROVIDED THE TERMINA TION CAP IS AT LEAST TWO 2 FEET 20 INCHES FOR DVP PIPE FROM A VERTICAL WALL AND 2 FEET BELOW A HORIZONTAL OVERHANG NOTE This also pertains to vertical vent...

Страница 34: ...igure 32 Proper Positioning Leveling and Securing of a Fireplace Figure 33 Gas Control System STANDING PILOT Step 5 The Gas Control Systems WARNING THIS UNIT IS NOT FOR USE WITH SOLID FUEL The gas con...

Страница 35: ...wrap does not exceed 2 in diameter and it does not penetrate the actual firebox Open the fireplace lower grille insert the gas supply line throughthegaslinehole andconnectittotheshut offvalve When at...

Страница 36: ...onal fan and remote control kits require that 110 120 VAC be wired to the factory installed junction box before the fireplace is permanently installed Wall Switch Position the wall switch in the desir...

Страница 37: ...OINT SIDE SEAL JOINT 0 1 4 FINISH MATERIAL MAY BE COMBUSTIBLE TOP AND SIDES OF UNIT Optional Accessories Optional fan and remote control kits require that 110 120 VAC be wired to the fireplace junctio...

Страница 38: ...ments of ANSI Z97 1 1984 and CPSC 16 CFR 1202 Safety Glazing Certification Council SGCC 1595 and 1597 Architec tural Testing Inc Reports 02 31919 01 and 02 31917 01 This statement is in compliance wit...

Страница 39: ...for light ing purposes The pilot is located inside the com bustion chamber If it is necessary to access the pilot remove the trim door and glass door THERMOCOUPLE PILOT THERMOPILE 5 To put the control...

Страница 40: ...e lines to purge themselves of this air Once the purging is complete the fireplace will light and will operate normally Subsequent lightings of the fireplace will not require this purging of air from...

Страница 41: ...ogs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your fireplace s flame patt...

Страница 42: ...le copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15mV replace the thermocouple b Defective valve If the thermocouple is producing more than 15 millivolts...

Страница 43: ...the unit The maximum downwards lope is 1 4 inch d Glass too loose and air tight packet leaks in corners after usage Tighten the corner e Bad thermopile or thermocouple Replace if necessary f Improper...

Страница 44: ...2 years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable it...

Отзывы: