![Viking VFR400 Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/viking/vfr400/vfr400_manual_1023432011.webp)
11
VFR-400 • 5403548 • REV W • 8/17
Service Use
NFPA 12 - Carbon Dioxide systems
NFPA 12A - Halon 1301 fire systems
NFPA 13 - Automatic Sprinkler
NFPA 15 - Water Spray Fixed System
NFPA 16 - Foam Water Sprinkler and Foam Water Spray
NFPA 17 - Dry Chemical
NFPA 17A - Wet Chemical
NFPA 72 - National Fire Alarm Code
• Local, Remote Station, Central Station (Protected premise unit)
NFPA
750
-
Water
Mist
NFPA 2001 - Clean Agent Fire Extinguishing System
Listings & Approvals
VFR-400 - UL Standard 864, ULC Standard S527, FM, CSFM, NYMEA, CE Marked and RoHS Compliant.
Terminals
• All terminals capable of handling #22-14 AWG wire
• All terminations have transient protection
• All four initiating device circuit terminals capable of handling linear heat detection.
Relay Outputs
• Common system alarm contacts SPDT rated 3 Amps, 30VDC resistive
• Common supervisory contacts SPST, N.O. rated 3 Amps, 30VDC resistive
• Common system trouble contacts SPDT rated 3 Amps, 30VDC resistive
• Common system waterflow contacts SPST, N.O. rated 3 Amps, 30VDC resistive
• Circuits connected to relays should be connected within the same room
Auxiliary Power
• Auxiliary Power - 24VDC Special Application. Rated 200 mA max. Power limited, current limited, non-supervised
• Resettable for 4-wire smoke detectors. Not to be used with CA2Z for 4-wire smoke detectors unless approved by local AHJ
Annunciator Connection
• Auxiliary Power - 24VDC Regulated. Rated 200 mA max. Power Limited, current limited non-supervised for RA-4410RC
Annunciator, non-resettable power
• RS-485 For connection to RA-4410RC remote annunciator
• Maximum 2000' with 22 AWG, 4000' with 20 AWG shielded cable
Optional Accessories - see technical data sheets in Annex A at the back of this manual
CA2Z Module (Class A Initiating Device Circuit)
Converts two Class B initiating device circuits to two Class A circuits. Not to be used for 4-wire smoke detectors unless approved
by local AHJ.
ARM-44 (Auxiliary Relay Module)
To provide 8 independent Form C outputs connected to panel via RS-485 and 24 VDC power.
CAM Module (Class A Indicating Appliance Circuit)
Converts indicating appliance circuit from Class B to Class A. One model CAM (Class A Module) is required
for each circuit. (Do not use this on an output programmed as “TROUBLE BELL”.)
ARM-1/ARM-2 Module (Auxiliary Relay Module)
Activated by 24VDC Indicating and/or Releasing, polarity reversing circuits. The module provides a non-supervised DPDT Relay
that can be used for fan shutdown, door release, elevator recall, etc.
RA-4410RC (Remote Annunciator)
Connects to RS-485 & 24
VDC terminals. Provides 34 LED’s for each zone in alarm supervisory, or trouble, each output activated
or in trouble, Power On, Power trouble, System trouble, Ground fault, Supervisory, Supervisory trouble, Alarm, Signal Silence
and Pre-discharge/Discharge.
RCDS-1 (Release Circuit Disconnect Switch)
Provides physical means of disconnecting release circuits in compliance with NFPA 72, 2007, 6.12.5.2.
BASIC OPERATION
In addition to the following events, the panel also provides an output via the RS-485 terminals to the RA-4410RC remote
annunciator to light the appropriate indicators. See remote annunciator operations, page 15. In addition, the remote annunciator
has a silenceable buzzer that sounds on supervisory or trouble conditions.
Содержание VFR400
Страница 67: ...67 VFR 400 5403548 REV W 8 17 This page intentionally left blank ...
Страница 98: ...98 VFR 400 5403548 REV W 8 17 ...
Страница 99: ...99 VFR 400 5403548 REV W 8 17 ...