3. PRODUCT DESCRIPTION
Viking Micromatic
®
Special Response
Sprinklers are small thermosensitive
glass bulb sprinklers available in various
finishes, temperature ratings, and orifice
sizes to meet design requirements.
During fire conditions, the heat-sensitive
liquid in the glass bulb expands, causing
the bulb to shatter, releasing the pip cap
and sealing spring assembly. Water
flowing through the sprinkler orifice
strikes the sprinkler deflector forming a
uniform spray pattern to extinguish or
control the fire.
4. TECHNICAL DATA
LISTINGS AND APPROVALS
Refer to the Approval Chart on pg 125 c.
Glass-bulb fluid temperature rated to
-65 °F (-55 °C).
Factory tested hydrostatically to 500 PSI
(3 448 kPa).
Min. Operating Pressure: 7 PSI (48,3
kPa)
Rated to 175 PSI (1 207 kPa) water
working pressure.
Testing: USA Patent No. 4,831,870
Response Time Index (RTI): 50-80 (ms)
½
SPRINKLER MATERIALS
Frame: Brass Castings UNS-C84400
Deflector: Brass UNS-C26000
Bulb: Glass, nominal 4 mm or 5 mm di-
ameter
Belleville Spring Sealing Assembly:
Nickel Alloy, coated on both sides
with Teflon Tape
Compression Screw: Brass UNS-C36000
Pip Cap: Brass UNS-C31600, or:
Pip Cap and Insert Assembly: Copper
UNS-C11000 and Stainless Steel
UNS-S30400
Polyester Coated Sprinklers:
Belleville Spring Sealing Assembly:
Exposed
Screw: Nickel Plated
AVAILABLE FINISHES
Brass, Chrome-Enloy
®
(patents pend-
ing), and White Polyester
ACCESSORIES
(order separately)
Sprinkler Wrenches:
A . S t a n d a r d W r e n c h : P a r t N o .
10896W/B (available since 2000) or
05000CW/B (no longer available)
B. Wrench for Coated and Recessed
Sprinklers: Part No. 07398W* (avail-
a b l e s i n c e 1 9 9 0 ) o r P a r t N o .
12144W/B** (available since 2003).
NOTE: Recessed pendent sprin-
klers with protective caps must
use wrench 12144W/B.
*A ½" ratchet is required (not available from Viking).
See the “Sprinkler Accessories” section
of the Viking data book.
5. INSTALLATION
WARNING:
Viking sprinklers are manu-
factured and tested to meet the rigid re-
quirements of approving agencies. The
sprinklers are designed to be installed in
accordance with recognized installation
standards. Deviation from the standards
or any alteration to the sprinkler after it
leaves the factory including, but not lim-
ited to: painting, plating, coating, or
modification, may render the sprinkler
inoperative and would automatically nul-
lify the approval and any guarantee
made by The Viking Corporation.
A. Viking sprinklers are to be installed
in accordance w ith the latest
edition of Viking technical data,
the latest standards of NFPA, FM
G l o b a l ,
L P C B ,
As s e m b l e e
Pleniere, VdS, or other similar or-
ganizations, and also with the pro-
visions of governmental codes,
ordinances, and standards when-
ever applicable.
The use of Special
Response sprinklers may be limited
due to occupancy and hazard. Refer
to the Authority Having Jurisdiction
prior to installation.
B. Sprinklers must be handled with care.
They must be stored in a cool, dry
place in their original shipping con-
tainer. Never install sprinklers that
have been dropped, damaged, or ex-
posed to temperatures exceeding
Form No. F_021396
Sprinkler 125 a
TECHNICAL DATA
November 18, 2005
MICROMATIC
®
SPECIAL RESPONSE
SPRINKLERS
Sprinkler Temperature
Classification
Nominal Sprinkler Temperature
Rating (Fusing Point)
Maximum Ambient
Ceiling Temperature
1
Bulb
Color
2
Ordinary
155 °F (68 °C)
100 °F (38 °C)
Red
Intermediate
175 °F (79 °C)
150 °F (65 °C)
Yellow
Intermediate
200 °F (93 °C)
150 °F (65 °C)
Green
High
286 °F (141 °C)
225 °F (107 °C)
Blue
Sprinkler Finishes:
Brass, Chrome-Enloy
®
, and White Polyester
1
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and
other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.
2
The temperature rating is stamped on the deflector.
Table 1
Pendent
Upright
Conventional
Replaces page 125 a-c, dated January 28, 2005
(5 mm glass bulb is an alternate).
OBSOLETE