Viking MICROFAST VK327 Скачать руководство пользователя страница 1

MICROFAST

®

 QUICK 

RESPONSE UPRIGHT 

SPRINKLER VK327 (K4.2)

TECHNICAL DATA

Page 1 of 3

Form No. F_061514      21.03.05    Rev 21.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1.  DESCRIPTION

The Viking Microfast

®

 Quick Response Upright Sprinkler VK327 is a small, 

thermosensitive, glass-bulb spray sprinkler available in several different finishes 

and temperature ratings to meet design requirements. The special Polyester and 

Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where 

colors are desired. In addition, these coatings have been investigated for installation 

in corrosive environments and are listed/approved as indicated in the Approval 

Chart(s).

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

Refer to Approval Chart(s) and Design Criteria for cULus Listing requirements 

that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)* 

Maximum Working Pressure: 175 psi (12 bar) wwp. 

Factory tested hydrostatic rating: 500 psi (34.5 bar)

Thread size: 1/2” NPT, 15 mm BSPT

Nominal K-Factor: 4.2 U.S. (57 metric**)

 

Glass-bulb fluid temperature rating: -65 °F (-55 °C)

Overall Length: 2-1/4” (58 mm)

 *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE 

Approvals ONLY is 5 psi (0.35 bar). 

Covered by the following US Patent No.: 4,831,870

Material Standards:

Frame Casting: Brass UNS-C84400

Deflector: Brass UNS-C23000 or Copper UNS-C19500

Bushing: Brass UNS-C36000

Bulb: Glass, nominal 3 mm diameter

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Screw: Brass UNS-C36000

Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400

For Polyester Coated Sprinklers:

 

Belleville Spring-Exposed

For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw-ENT Plated, Pip Cap-ENT Coated

Ordering Information:

 (Also refer to the current Viking price list.)

Order Viking Microfast

®

 Quick Response Upright Sprinkler VK327 by first adding the appropriate suffix for the sprinkler finish and 

then the appropriate suffix for the temperature rating to the sprinkler base part number. 

Finish Suffixes: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B and ENT = JN

Temperature Suffixes: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, and 286 F° (141 °C) = G

For example, sprinkler VK327 with a 1/2” NPT thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 06719BAB

Available Finishes And Temperature Ratings: 

Refer to Table 1.

Accessories:

 (Also refer to the current Viking price list.)

Sprinkler Wrench: 

Standard Wrench: Part No. 21475M/B (available since 2017)

 

Sprinkler Cabinets:

A. Six-head capacity: Part No. 01724A (available since 1971)

B. Twelve-head capacity: Part No. 01725A (available since 1971)

4.  INSTALLATION

Refer to appropriate NFPA Installation Standards.

Replaces Form F_061514 Rev 20.1

(Removed bushed part numbers)

Содержание MICROFAST VK327

Страница 1: ... operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Covered by the following US Patent No 4 831 870 Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C23000 or Copper UNS C19500 Bushing Brass UNS C36000 Bulb Glass nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw Brass UNS C36000 Pip Cap and Insert A...

Страница 2: ...inkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 F 57 C 100 F 38 C Orange Ordinary 155 F 68 C 100 F 38 C Red Intermediate 175 F 79 C 150 F 65 C Yellow Intermediate 200 F 93 C 150 F 65 C Green High 286 F 141 C 225 F 107 C Blue Sprinkler Finishes Brass Chrome White Polyester Black Polyester and ENT3 4 Corrosion Resis...

Страница 3: ...tional approvals 4 Listed by Underwriters Laboratories Inc for us in the U S and Canada 5 Other colors are available on request with the same Listings and Approvals as the standard colors 6 cULus Listed as corrosion resistant DESIGN CRITERIA Also refer to Approval Chart 1 above cULus Listing Requirements The Viking Microfast Quick Response Upright Sprinkler VK327 is cULus Listed as indicated in Ap...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...