1. PRODUCT NAME

VIKING Microfast

®

 Model M-4

Small Orifice 
Residential Pendent Sprinkler

2. MANUFACTURER

THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058, USA
Telephone: (616) 

945-9501

(800) 968-9501

Fax No: 

(616)  945-9599

From outside the U.S.A.:
Telephone: +1 (616) 945-9501
Fax No: 

+1 (616)  945-9599

e-mail:  [email protected]

3. PRODUCT DESCRIPTION

The Viking Microfast

®

 Model M-4 Small

Orifice Residential Pendent Sprinkler is
a small, high-sensitivity, glass-bulb
spray sprinkler.  The sprinkler is avail-
able in several finishes, with tempera-
ture ratings to meet design require-
ments.  The sprinkler is listed for use
below smooth, flat, horizontal ceilings
and ceilings with slopes up to and in-
cluding a 6/12 pitch.  (26.

6°)  T

he small

orifice design, with a K Factor of 4.3,
allows efficient use of available water
supplies for the hydraulically designed
fire-protection system. The small, rug-
ged, 3mm glass-bulb and special deflec-
tor combine speed of operation and ar-
eas of coverage to meet residential
sprinkler standards. During fire condi-
tions, the heat-sensitive liquid in the
glass bulb expands, causing the glass to
shatter, releasing the pip cap and seal-
ing spring assembly.  The water flowing
through the sprinkler orifice strikes the
sprinkler deflector, forming a uniform
spray pattern to extinguish or control the
fire.

4. TECHNICAL DATA

See chart for approvals.
See chart for minimum water supply re-

quirements and maximum areas of
coverage.

Glass-bulb fluid temperature rated to  

-

65°F (-55°C).

Rated to 175 PSI (1 207 kPa) water

working pressure.

Factory tested hydrostatically to 500 PSI

(3 448 kPa).

Spring: USA Patent No. 4,167,974
Bulb: USA Patent No. 4,796,710
Testing: USA Patent No. 4,831,870
Thread Size: 1/2" (15 mm) NPT
K Factor:  4.3 (6,2 Metric*)

*See Footnote 8 on approval chart.

SPRINKLER MATERIALS:
Frame -  Brass Castings UNS-C84400

Form No. F_082095

Sprinkler 140 a

June 4, 1998

TECHNICAL DATA

Replaces sprinkler page 140 a-c, dated August 25, 1997
(updated approved finish and escutcheon lists).

           APPROVED 

                                                        APPROVED FINISHES                    APPROVED ESCUTCHEONS   

      TEMPERATURES

  1:  Brass, Bright Brass, Chrome-         X: Standard surface or F-1 Adjustable 

      A: 155° F (68°C)                      Enloy

®

, White (Paint), and                  Escutcheon, or recessed with

       and 175° F (79° C)

       Navajo White                                       E-1 Recessed Escutcheon 

     

3

 Base part number shown.  For complete part number, see price list.

4

 This chart shows the listings and approvals available at the time of printing.  Other approvals are

   in process.  Check with the manufacturer for any additional approvals.

5

 Listing is for residential occupancies with smooth, flat, horizontal ceilings.

6

 Listing is for residential occupancies with smooth ceilings with slopes up to and including a 6/12 

       (26.6°) pitch.  

7

 Listed by Underwriter’s Laboratories, Inc. for use in Canada.

8

 Acceptance for use by City of New York Department of Buildings is pending.

9

 For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" for the

  next largest area listed with sprinklers of similar K factor.

10

 Areas under sloped ceilings must be measured along the ceiling slope.  Actual floor coverage under

    sloped ceilings will be less than the listed Area of Coverage.

11

 Metric K Factor shown is for use when pressure is measured in kPa.  When pressure is measured in

       BAR, multiply the metric K Factor shown by 10.0.

12

 The Model F-1 Adjustable Escutcheon is considered a surface-mounted escutcheon because it does

    not allow the fusible element of the sprinkler to be recessed behind the face of the wall or ceiling.

NOTE: Install residential pendent sprinklers with deflectors between 1" (3/4" for recessed) & 4" below

the ceiling.

Maximum Areas

    Minimum Water Supply Requirements

of Coverage

9

  Single Sprinkler  

       Two or More

UL

5

       ULC

      NYC

12’ X 12’   

 11.5 GPM @ 7.2 PSI 

    11.5 GPM @ 7.2 PSI        

3.7m X 3.7m   

43,5 L/Min @  49,3 kPa

  43,5 L/Min @  49,3 kPa

A1X         A1X   

   --  

14’ x 14’   

13 GPM @ 9.1 PSI

    11.5 GPM @ 7.2 PSI 

4.3m x 4.3m   

49,2 L/Min @ 63,0 kPa

  43,5 L/Min @  49,3 kPa

A1X         A1X   

   --  

16’ x 16’   

13 GPM @ 9.1 PSI

    11.5 GPM @ 7.2 PSI

A1X         A1X   

   --

4.9m x 4.9m  

49,2 L/Min @ 63,0 kPa

  43,5 L/Min @ 49,3 kPa

 

       

18’ x 18’   

16 GPM @ 13.8 PSI

    13.5 GPM @ 9.9 PSI

A1X         A1X   

   --

5.5m x 5.5m   

60,6 L/Min @ 95,6 kPa

  51,1 L/Min @ 68,0 kPa

  

 

20’ x 20’  

19 GPM @ 19.5 PSI

    17 GPM @ 15.6 PSI

A1X         A1X   

   --

6.1m x 6.1m  

71,9 L/Min @ 134,6 kPa

  64,4 L/Min @ 107,8 kPa

 

                      Sloped Ceiling Approvals

10

   

 Maximum Area

   Minimum Water Supply Requirements 

of Coverage

9,10 

Single Sprinkler 

        Two or More

UL

5

       ULC

7

     NYC

8

16’ X 16’

 18 GPM @ 17.5 PSI 

    13 GPM  @  9.1 PSI  

  

4.9m X 4.9m

68,1 L/Min @ 120,7 kPa

  49,2 L/Min @ 63,0 kPa 

   

A1X         A1X  

 --  

   

Deflector

Thread

Nominal

    Overall

Style

Size NPT

K Factor

11

    Length

Base Part Number

3

1/2 inch 

4.3 US

   2.25 inch

Pendent

(15mm)

(6,2 metric)

   (57,2mm)

09530

                                     AREAS OF COVERAGE

4

SAMPLE

Temperature
Finish

        A1X

Escutcheon

Sprinkler

Nominal Sprinkler

                                          Ceiling Temperature at Sprinkler 

Temperature 

 Temperature 

Rating

 

Max. Ambient           Max. Recommended           

 Bulb  

    Classification          (Fusing Point)   

     Temp. Allowed

1

           Ambient Temp.

2

    

Color

 Ordinary   

155°F (68°C)  

 135°F (46°C) 

 100°F (38°C)

 Red

Intermediate  

175°F (79°C)  

155°F (68°C) 

150°F (65°C)

Yellow

Sprinkler Finishes:  Brass, Bright Brass, Chrome-Enloy

®

 (patents pending), White(Paint), and Navajo

                                   White(Paint)

1

 Based on National Fire Prevention and Control Administration, Contract No. 7-34860.

    

 2

 Based on NFPA-13. Other limits may apply depending on fire loading, sprinkler location, and other 

       Authority-Having-Jurisdiction requirements.  Refer to specific installation standards. 

MICROFAST

®

 MODEL M-4

SMALL ORIFICE RESIDENTIAL

PENDENT SPRINKLER

OBSOLETE