VK3101 QUICK RESPONSE 

CONVENTIONAL 

SPRINKLER (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 1 of 3

Form No. F_102818    Rev 22.1     March 3, 2022

1.  DESCRIPTION

The Viking VK3101 Quick Response Conventional Sprinklers are small, thermosensitive, 

glass-bulb spray sprinklers available in several different finishes, temperature ratings, 

and K-factors to meet design requirements. The special Polyester, and Electroless 

Nickel Polytetrafluoroethylene (ENT), coatings can be used in decorative applications 

where colors are desired. In addition, these coatings have been investigated for 

installation in corrosive environments and are listed as indicated in the Approval 

Chart. 

Quick Response sprinklers may be ordered and/or used as open sprinklers (glass bulb 

and pip cap assembly removed) on deluge systems. Refer to Ordering Information.

2.  LISTINGS AND APPROVALS

cULus Listed: 

Category VNIV

LPCB Approved 

reference no. 096m

*  Refer to the Approval Chart and Design Criteria for Listing requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)

Rated to: 175 PSI (12 bar)

Factory tested hydrostatically to 500 psi (34.5 bar).

Thread size: 1/2” NPT or 15 mm BSPT

Nominal K-factor: 5.6 U.S. (80.6 metric**)

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

** Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Material Standards:

Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass

Deflector: Stainless Steel UNS S30400

Pip Cap Shell - Stainless Steel UNS-S44400 

Pip Cap Disc - Stainless Steel UNS-S30100 

Belleville Spring - Nickel Alloy

Pip Cap Seal - Polytetrafluoroethylene (PTFE)

Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000

Shipping Cap: Polyethylene

Bulb: Glass, nominal 3 mm diameter

Ordering Information:

 

(Refer to Table 1.)

4.  INSTALLATION

Refer to appropriate NFPA and/or any other applicable installation standards.

NOTICE

Risk of permanent damage.

Over-tightening the sprinkler can cause permanent damage.

 

> Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs. (19.0 N-m).

5.  OPERATION

During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and 

sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern 

to extinguish or control the fire.

6.  INSPECTIONS, TESTS, AND MAINTENANCE

Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7.  AVAILABILITY

The Model VK3101 Sprinkler is available through a network of domestic and international distributors. See the web site for the 

closest distributor or contact Viking.

8.  GUARANTEE

For details of warranty, refer to the current list price schedule or contact us directly.

Replaces Form No. F_102818 Rev 21.1 

(Added LPCB details, removed CE.)

Содержание 23908

Страница 1: ...6 U S 80 6 metric Glass bulb fluid temperature rated to 65 F 55 C Metric K factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa divide the metric K factor sho...

Страница 2: ...ature of 100 F 38 C meaning if the area will experience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A I...

Страница 3: ...CB or other similar organizations and also with the provisions of governmental codes ordinances and standards whenever applicable Figure 3 Installation Frame arms parallel to the pipe 1 2 3 1 Slide th...

Страница 4: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 5: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 6: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 7: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 8: ...readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification...

Страница 9: ...y intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler...

Страница 10: ...ENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking C...

Страница 11: ...e sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any s...

Страница 12: ...ctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements...

Страница 13: ...her To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVI...

Страница 14: ...rior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service d...

Страница 15: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Страница 16: ...render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERA...

Отзывы: