background image

VK1021 STANDARD 

RESPONSE PENDENT 

SPRINKLER (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 1 of 6

Form No. F_020416     Rev 22.1     March 3, 2022

1.  DESCRIPTION

The Viking VK1021 Standard Response Pendent Sprinkler is a small thermosensitive 

glass bulb spray sprinkler available with various finishes and temperature ratings

to meet design requirements. The special Polyester and Electroless Nickel PTFE

(ENT) coatings can be used in decorative applications where colors are desired.

In addition, these coatings have been investigated for installation in corrosive

environments and are Listed and Approved as indicated in the Approval Chart.

2.  LISTINGS AND APPROVALS

cULus Listed:

 Category VNIV

FM Approved: 

Classes 2017, 2015, 2043

Also approved for use in FM Approved vacuum dry sprinkler systems with a 

maximum supervisory vacuum pressure of -3 psi (-207 mbar).

CE:

 Standard EN12259-1, DOP_XT1A

LPCB Approved 

reference no. 096m

VdS Approved 

Certificate no. G 422004

Refer to the Approval Chart and Design Criteria for requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)

Rated to: cULus  - 250 PSI (17 bar)  WWP

 

        FM, LPCB, and VdS - 175 PSI (12 bar)  WWP

Factory tested hydrostatically to 500 psi (34.5 bar)

Thread size: 1/2” NPT (15 mm BSPT)

Nominal K-factor: 5.6 U.S. (80.6 metric*)

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

*  Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Material Standards:

Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass

Deflector: Stainless Steel UNS S30400

Pip Cap Shell - Stainless Steel UNS-S44400 

Pip Cap Disc - Stainless Steel UNS-S30100 

Belleville Spring - Nickel Alloy

Pip Cap Seal - Polytetrafluoroethylene (PTFE)

Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000

Shipping Cap: Polyethylene

Bulb: Glass, nominal 5 mm diameter

Ordering Information: (Refer to Table 1 and the current Viking List Price Book.)

4.  INSTALLATION

Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards.

NOTICE

Risk of permanent damage.

Over-tightening the sprinkler can cause permanent damage.

 

> Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs. (19.0 N-m).

5.  OPERATION

During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the 

glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes 

the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.

Replaces Form No. F_020416 Rev. 21.3

(Added LPCB and VDS details)

Содержание 23868

Страница 1: ...ng Pressure 7 psi 0 5 bar Rated to cULus 250 PSI 17 bar WWP FM LPCB and VdS 175 PSI 12 bar WWP Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 NPT 15 mm BSPT Nominal K factor 5 6 U...

Страница 2: ...ience temperatures above the maximum ambient rating you shall use a higher temperature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 available since 2017...

Страница 3: ...155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C B 135 F 57 C 155 F 68 C 175 F 79 C and 200 F 93 C C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C D 155 F 68 C 175 F 79 C and 200 F 93 C Approved Fi...

Страница 4: ...t edition of Viking Technical Data the appropriate standards of NFPA LPCB APSAD VdS CE MED or other similar organizations and also with the provisions of governmental codes ordinances and standards wh...

Страница 5: ...e 3 Recessed Installation with Recessed Socket Wrench A 1 2 ratchet is required not available from Viking Figure 4 Recessed Installation with standard Installer s Wrench 2 Carefully slide the wrench s...

Страница 6: ...ctive cap then push upwards to engage with the sprinkler wrench flats 3 Install the sprinkler and escutcheon assembly into the pipe fitting Be sure the escutcheon contacts the surface of the finished...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification...

Страница 12: ...y intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler...

Страница 13: ...ENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking C...

Страница 14: ...e sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any s...

Страница 15: ...ctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements...

Страница 16: ...her To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVI...

Страница 17: ...rior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service d...

Страница 18: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Страница 19: ...render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERA...

Отзывы: