Viking 15166 Скачать руководство пользователя страница 1

ESCUTCHEON

INSTALLER TOOL

TECHNICAL BULLETIN

June 6, 2008

The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058

Telephone:  269-945-9501 Technical Services 877-384-5464  Fax:  269-945-4495  Email:  [email protected]

INSTRUCTIONS FOR USING THE ESCUTCHEON INSTALLER TOOL

Viking

 

Model E-1 Recessed and F-1 Adjustable Escutcheons may be installed onto Viking

  

sprinklers using Escutcheon Installer Tool 

Part Number 15166. To use the escutcheon installer, attach a length of 1” diameter CPVC tubing to the tool, as shown in Figure 1 

below.

Step 1:

 Install the sprinkler and escutcheon adapter according to the Installa-

tion Instructions provided in the appropriate technical data page for the 
sprinkler model being used.

NOTE: 

Sprinklers with protective caps or bulb shields must be contained within 

the caps or shields.

Step 2: 

After the ceiling is installed and the proper size hole is cut, attach the 

escutcheon cup using the Escutcheon Installer Tool. Refer to Figures 2 and 3. 

a.  Remove the escutcheon cup from the protective box and attach it to the Escutcheon Installer Tool.
b.  Gently place the escutcheon cup over the sprinkler protruding through the opening in the ceiling.
c.  Press on the outer escutcheon cup until the flanges touch the surface of the ceiling.
d. Pull to release the cover installer from the cover plate.

For precise installation, the Escutcheon Installer Tool is adjustable to match the amount the sprinkler is recessed above the ceiling. 

Simply turn the tool clockwise or counterclockwise.  

NOTE:

 With the Model E-1 Recessed Escutcheon, the maximum adapter recess is 5/8” (16 mm). With the Model F-1 Adjustable 

Escutcheon, the maximum recess is ¼” (6.4 mm). Note: The face of the escutcheon adapter may extend up to ¼” (6.4 mm) 
beyond the edge of the escutcheon cup, resulting in ½” (12.7 mm) total adjustment range.

DO NOT modify the unit. If necessary, re-cut the sprinkler drop nipple as required.

Step 3:

 Remove plastic protective sprinkler caps and bulb shields AFTER the ceiling finish work is completed where the sprinkler 

is installed and there no longer is a potential for mechanical damage to the sprinkler operating elements. To remove the bulb 
shields, simply pull the ends of the shields apart where they are snapped together. To remove caps from frame style sprinklers, 
turn the caps slightly and pull them off the sprinklers. 

SPRINKLER CAPS AND BULB SHIELDS MUST BE REMOVED FROM 

SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! 

NOTE:

 The effectiveness of using a CPVC pipe longer than 12 ft. may be significantly reduced.

Refer to the latest appropriate technical data pages for complete care, handling, and installation instructions. Data pages are included with each ship-

ment from Viking or Viking distributors. They can also be found in your Viking technical data book and on the Web site at www.vikinggroupinc.com.

Figure 2:

Use the tool to install the

Model E-1 or F-1 Escutcheon

cup on the sprinkler and adapter.

Figure 1:

Attach the Escutcheon Installer 

Tool onto the end of CPVC

pipe. Place an escutcheon

cup in the installer tool.

Form No. F_051808

New sprinkler bulletin, issued June 6, 2008.

Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

Figure 3:

Press the escutcheon cup

onto the adapter until the

flanges touch the ceiling.