P/N 3101072 • REV 04 • REB 24JAN13 

 

V-HFD Fixed-Temperature Heat Detector 
Installation Sheet 

EN  FR 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

EN: Installation Sheet 

Operation 

The V-HFD Fixed-Temperature Heat Detector is an intelligent 
analog device that contains a 135°F (57°C) fixed-temperature 
heat sensor to detect heat from fire. The heat sensor monitors 
the temperature of the air in its surroundings and determines 
whether to initiate an alarm. The detector is capable of 
performing comprehensive self-diagnostics and storing the 
results. 

LED operation 

The detector provides a bicolor LED that shows its status. 

Normal: Green LED flashes 

Alarm/active: Red LED flashes 

Electronic addressing 

The control panel automatically assigns addresses to the 
detectors. Use a laptop computer to address custom 
addresses to the detectors. No addressing switches are used. 

Installation 

Refer to 

Smoke and Heat Detector Application Bulletin

  

(P/N 3101109) for additional information on detector placement 
and spacing. 

WARNINGS 

• 

This detector does not operate without electrical power. As 
fires frequently cause power interruption, discuss further 
safeguards with the local fire protection specialist. 

• 

This detector does not sense fires in areas where smoke 
cannot reach the detector. Smoke from fires in walls, 
roofs, or on the opposite side of closed doors may not 
reach the detector. 

• 

This detector is intended for use with ionization and/or 
photoelectric smoke detectors. The heat detector by itself 
does not provide life safety protection. 

• 

This detector does not detect oxygen levels, smoke, toxic 
gases, or flames. Use this device only as part of a broad-
based, life-safety program which includes a variety of 
information sources pertaining to heat and smoke levels, 
extinguishment systems, visual and audible devices, and 
other safety measures. 

• 

Independent studies recommend using heat detectors only 
for property protection. Never rely on heat detectors as the 
sole means of fire protection. 

• 

To ensure proper operation, schedule maintenance 
(regular or selected) in accordance with the requirements 
of the authority having jurisdiction. Refer to NFPA 72 and 
CAN/ULC−S536. 

• 

To ensure proper operation, store the detector within the 
recommended ranges. Allow the detector to stabilize to 
room temperature before applying power. 

• 

Keep the dust cover (supplied) on the detector during 
installation and remove it prior to commissioning and 
service. The dust cover is not a substitute for removing the 
detector during new construction or heavy remodeling. 

To install the detector: 

1.  Install and wire the detector base using the installation 

sheet supplied with the detector base. 

2.  Connect the detector to the base by rotating the detector 

clockwise until it snaps into the locked position. 

The head can be removed by turning it counterclockwise. 

3.  If the head must lock to the base, break away the locking 

tab using a pair of pliers. See Figure 1. 

To then remove the detector head after breaking away the 
locking tab, insert a small screwdriver into the slot on the 
side of the base and press in while simultaneously turning 
the detector head counterclockwise. 

4.  Log the serial number on the appropriate worksheet. 