Document: LT0439 Vigilant
MX1-Au
Operator Manual
Issue 1.73
23 October 2018
Page 8-5
From the base display press MENU three times then
MX LOOP
F2 to
view the
MX
Loop Status.
Equipment : 8 Ver 2.00 |
MX Loop : 40.7V, 0.0A | PREV
Return : 40.3V |
NEXT
| DEVICES
Fig 8-5 –
MX
Loop Status
Equipment
: shows which
MX
loop is being viewed. 1 is the on-
board loop and 2 onwards are the optional
MX
Loop Cards. The
firmware version for each
MX
Loop Card will be included. Press
PREV
F2 or
NEXT
F3 to switch between loops.
MX Loop
: is the voltage and current being fed to the loop wiring.
Return
: the voltage at the return end of the loop.
Normally the power is fed via the AL terminals and the loop return
voltage is measured at the AR terminals. In this situation the points
described below will all be normal.
Under fault conditions, the power feed may be switched to the AR end
(for a short circuit at the AL terminals), or feed via both ends (for an open
circuit in the loop, or a short circuit between two short circuit isolators).
Fig 8.5 shows a typical situation. The power feed is applied to the start
of the loop, which is drawing only a light load current. The voltage at the
end of the loop is being monitored to detect any breaks in the wiring.
If power is being fed to the AR side, the Return voltage displayed will be
0V. If the loop is drawing too much current, the
MX
Loop voltage display
will also be 0V. A more detailed assessment of the
MX
Loop condition
can be gained from the presence of these points in the fault list (refer to
Chapter 11
(“Equipment Point Descriptions”) for details).
MX Loop Left S/C
– is in Fault if there is a short circuit between
the AL+ and AL- terminals.
MX Loop Right S/C
– is in Fault if there is a short circuit between
the AR+ and AR- terminals.
MX Loop Open Circuit
– is in Fault if there is an open circuit in
the loop wiring. Note that an activated short circuit isolator will also
register as an open circuit fault.
MX Loop Overload
– is in Fault if too much current is being drawn
by the
MX
Loop. The normal capacity for each loop is 1A.
Press
IR CTRL
F1 to access the infrared commands. Note this
command requires operator Access Level 2.
MX Loop Status
Viewing Loop
Status
IR CTRL
Содержание MX1-Au
Страница 104: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 8 18 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 118: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 9 14 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 160: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 11 34 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 182: ...Vigilant MX1 Au Operator Manual Document LT0439 Page 23 October 2018 Issue 1 73 12 22 THIS PAGE INTENTIONALLY LEFT BLANK...