Document: LT0109
Vigilant MICROVAC Owner's Manual
Installation, Wiring, Setup, and Commissioning
Issue 1.31
5 April 2000
Page 2-1
CHAPTER 2
INSTALLATION, WIRING, SETUP &
COMMISSIONING
2.1 INSTALLATION
The MICROVAC control unit should be mounted on a wall in a location convenient to the
provision of:
- 240V Mains
- Speaker & Strobe Cabling
- FIP and BGA interconnection cabling
- BGM and PAGING interconnection cabling if required
- Easy Operation
- It is desirable to allow the door to open fully to allow easy access inside the cabinet.
2.2 WIRING
2.2.1 MAINS
240V Mains wires into the unit via one of the cable entry holes in the top or bottom of the
case.
Mains earth terminates on the earth stud and phase and neutral on terminals 2 and 3 of the
Mains ON/OFF switch respectively. On models with a PSU2406 fitted, mains connects to the
mains cord fitted to the PSU2406.
2.2.2 BATTERIES
For the FP0530, FP0533, and FP0626 (which use the Microvac main board PSU) a 24V
battery must be connected to screw terminals J5 and J6.
J5 Bve
J6 Battery -ve
For the remaining models (which use a PSU2406) a 24V battery must be connected to the
battery leads of the PSU2406
Red
Bve
Black Battery -ve
2.2.3 AUXILIARY 24V OUTPUT
The internal 24Vdc supply is available on screw terminals J7 - J10:
J7 +24Vdc
(Unprotected - for voltmeter)
J8 0V
J9 +24Vdc
(Fused - for auxiliary loads)
J10 0V