TSFC 12-2 User Manual
Vighnaharta Technologies Pvt. Ltd. Page
20
of
26
3
System Programming
The fire panel system is completely programmable at site with the help of panel keypad and LCD.
It does not require software skills OR any special software for Programming.
When panel is in normal state, the screen displays as below. Normal state means all zone of panel
are in enabled and panel is fault free.
TrueSafe
SYSTEM OK
To enter the programming mode, panel must be in normal condition as above. If any fault or alarm
condition exists, make sure that it is cleared and panel returns to normal condition. Users should
have Key lock passwords. Without key lock password user cannot enter in MENU function. Factory
default panel do not have any password. If user enables
“Auto Key Lock” function
, only that time
panel will ask password. (Factory default password is “1111”)
To enter into Programming mode do following steps,
1.
Press
MENU
key
, it will ask for password (If “Auto Key Lock” function is enable
d)
2.
Enter FOUR digit numeric passwords.
3.
After entering the password user can access all MENU functions
4.
If password is incorrect, the LCD displays will show below screen,
Password Invalid
****
3.1
Menu Options
There are total 7 programming menu options as listed below.
❖
Use
and
keys to show the
next menu options.
❖
Press
ENTER
key to entering sub menu
OR “enable/disable” function
❖
Press
key to return to previous menu OR
Exit menu
ZONE1 Configuration
ZONE2 Configuration
NAC Mode
NAC Auto Silence
Auto Key Lock
Password Configuration
Wi-Fi Configuration