Installation Guide

QDM-05-000045

Rev 8 | July 2022 

  

©

2022 View, Inc.

Sky Sensor Installation Guide 

Work Performed By:  

Low-Voltage Electrician

Sky Sensor Body

Sky Sensor Base

The roof-mounted Sky Sensor 

provides external light level data 

and infrared temperature data to the 

View system to allow optimization 

of tint levels for each zone. The 

assembly includes the Sky Sensor 

with a 4 ft. length of CAT5 Ethernet 

cable attached.

Package Includes 

1.  Sky Sensor Assembly

• 

View Net (P/N: VN-SKY)

• 

CSS (P/N: 005-101418) 

 

2.  Sky Sensor Installation Kit (P/N: VN-SMK)

Tools and Materials Required

1. 

3/4” Rigid Metallic Tubing (RMT) for roof mast, brackets, flashing and sealant.

2. 

#2 Phillips screwdriver

3.  Cutting, Drilling and Deburring tools.
4. 

Wire stripping tools.

5. 

Wrenches.

6.  Grounding wire: 12 AWG THHN green or green/yellow
7. 

300 ft Unshielded Plenum CAT5 ethernet cable spool, modular connectors and crimping tool.

8.  Standard Junction box (10 x 10 x 6”), CSS Only
9. 

CAT5 Ethernet tester

Additional Supporting Documentation

1. 

Sky Sensor Data Sheet - QDM-02-000247

2. 

CP5.5 Data Sheet - QDM-02-000244

3. 

CP5.0 Data Sheet - QDM-02-000219

4. 

CP2.0 Data Sheet - QDM-02-000033

Содержание Sky Sensor

Страница 1: ... View Net P N VN SKY CSS P N 005 101418 2 Sky Sensor Installation Kit P N VN SMK Tools and Materials Required 1 3 4 Rigid Metallic Tubing RMT for roof mast brackets flashing and sealant 2 2 Phillips screwdriver 3 Cutting Drilling and Deburring tools 4 Wire stripping tools 5 Wrenches 6 Grounding wire 12 AWG THHN green or green yellow 7 300 ft Unshielded Plenum CAT5 ethernet cable spool modular conn...

Страница 2: ... 2 feet above the highest obstruction on the roof of the building Provide 360 degree unobstructed view horizontal 4 Ensure mounting height will not be obscured based on average snowfall 5 Mounting system must be bonded to building ground at the location of electrical junction box 6 Verify mounting location in field with building owner and View Interconnect Drawings 7 Mounting system and mast needs...

Страница 3: ...r the top of the mast so that a cable can be routed through the mast and not cause damage to the cable 3 Install electrical junction box EJB to the top of the mast see Best Known Methods 4 Add included pipe to top of the EJB for the sky sensor base assembly make a mark 1 1 4 from the top of this pipe as shown Make sure the top of the sky sensor is 2 feet above the highest obstruction on the roof 5...

Страница 4: ... step 3 Slide the Sky Sensor base down onto the galvanized steel pipe and ensure the bottom of the Sky Sensor Base lines up with the mark that you made 1 1 4 from the top If the two align this indicates that the pipe is fully inserted into the Sky Sensor 4 Hand tighten the three set screws until firmly secured to the pipe Note Do not over tighten and strip the screws Do not use power tools 5 Using...

Страница 5: ...ground If there is any doubt on the proper facility ground point consult with the electrician on site 4 Route the ethernet cable from the EJB to the Standard Junction Box Connect the cable to the RJ45 Jack labeled as IN IN of each surge protector Note Test the cable like in step 2 5 5 Connect the extension Ethernet CAT6 unshielded cable UTP from the RJ45 Jack labeled as OUT to port J18 on top of t...

Страница 6: ...r green yellow wire ground the surge protector to the CP5 0 as shown Note Preferably ground to a single ground stud Use the provided star washer 6 Route the ethernet cable from the EJB to the CP through the CP s overhead cable entry slot as shown Connect the cable to the RJ45 Jack labeled as IN IN of each surge protector Note Test the cable like in step 2 5 7 Connect the extension Ethernet CAT6 un...

Страница 7: ...rovided 12AWG THHN green or green yellow wire ground the surge protector to the CP5 5 as shown 5 Route the ethernet cable from the EJB to the CP through the CP s overhead cable entry slot as shown Connect the cable to the RJ45 Jack labeled as IN IN of each surge protector Note Test the cable like in step 2 5 6 Connect the extension Ethernet CAT6 unshielded cable UTP from RJ45 Jack labeled as OUT t...

Страница 8: ...y Sensor Body Step 5 Connect Data Cable to Sky Sensor 1 Remove the dust cap from the CAT5 ethernet cable inside the Sky Sensor Base on the mast 2 Align the RJ 45 connector and the keying feature see below and small hole on the bottom of the Sky Sensor Once aligned carefully press the two together and hand tighten the black colored sleeve securely to the base of the Sky Sensor Step 4 Prepare the Sk...

Страница 9: ...ensor place it onto the Sky Sensor Base 2 Using a Phillips screwdriver tighten the three set screws on the Sky Sensor to secure it to the Sky Sensor base The screw will thread into the base until the head of the screw bottoms out on the wall of the sensor it does not need to be tightened past this point Step 7 Sky Sensor Verification 1 Contact View Costumer Support to verify connectivity ...

Страница 10: ...Sensor Gore Patch Step 8 Final Operation Preparation 1 Using an optical cleaning wipe clean the sensors on the sides and top of the Sky Sensor Ensure all sensors are free of dust debris and oils from fingers 2 Ensure the Gore Patch on the side of the sensor is not damaged taped over or covered by silicone ...

Страница 11: ...11 Rev 8 July 2022 2022 View Inc All rights reserved Sky Sensor Installation Guide Best Known Methods ...

Страница 12: ...12 Rev 8 July 2022 2022 View Inc All rights reserved Sky Sensor Installation Guide Best Known Methods CP Sky Sensor ...

Отзывы: