86
6.
Confirm with
.
Connection is established.
Explanation of displays:
Connection active
No connection
Deactivating the WiFi connection
WiFi is automatically deactivated:
■
If no data transfer takes place for 30 minutes follow-
ing connection to a WiFi enabled device.
or
■
After 5 minutes if no connection to a WiFi enabled
device is established.
Service display
Service limits can be set in parameters "1F", "21" and
"23" in the
"Boiler"
group.
Once these values have been reached, a service mes-
sage appears on the display.
Acknowledging the service display
Tap the following buttons:
flashes in the navigation area.
Calling up acknowledged service messages
Tap the following buttons:
1.
in the navigation area
If fault messages are also present, the following
will appear after tapping on
:
"Fault list"
and
"Service messages"
2. "Service messages"
Service messages are shown in yellow and appear
in chronological order in a list.
Resetting the service message
If a service is carried out
prematurely
, set parameter
"24:0" in the
"Boiler"
group to "24:1", and then back to
"24:0". The selected service parameters for hours run
and time intervals restart at 0.
Tap the following buttons:
1.
2. "Service"
3.
Enter the password "viservice".
4. "Service functions"
5. "Reset service"
The set service parameters for hours run and inter-
val restart at 0 and parameter "24" in the
"Boiler"
group is set to "24:0".
Note
If parameter "24" is not reset once service is com-
plete,
"Service"
will be displayed again on the fol-
lowing Monday.
Diagnosis and service scans
Enabling the service interface for Vitosoft…
(cont.)