26
To match the burner output to the system flue pipe
length, a correction factor can be set.
0
1.
Tap
MODE
.
0
2.
/ repeatedly until
CONFI
flashes.
0
3. OK
to confirm.
"P" is displayed in the l.h. display area. The r.h.
display area flashes.
0
4.
Use / to select "12".
0
5. OK
to confirm.
"1" flashes in the l.h. display area.
0
6.
Use / to select "3".
0
7. OK
to confirm.
The selected correction factor flashes in the r.h.
display area.
0
8.
Refer to the following table for the correction factor
required for the connected flue system.
0
9.
Use / to change the correction factor.
10. OK
to confirm. The selected value is adopted.
Correction factor
0
1
2
3
4
5
6
Flue system
Rated heat-
ing output
(kW)
Max. pipe length (m)
Open
flue operation
7
60 mm
26
3
12
15
—
—
—
—
35
4
9
15
22
25
—
—
Room sealed
operation
7
60/100 mm
coaxial
26
2
6
11
16
20
—
—
35
2
5
8
12
16
25
—
Open
flue operation
7
80 mm
26
16
25
—
—
—
—
—
35
11
25
—
—
—
—
—
Room sealed
operation
7
80/125 mm
coaxial
26
5
20
25
—
—
—
—
35
5
13
22
25
—
—
—
Burner adjustment when connecting multiple flues to a shared flue system
When connecting several Vitodens 111-W to a shared
flue system:
Adjust the burner settings of each connected boiler by
a correction factor to match it to the flue system.
System conditions:
■
Shared flue in shaft
7
100 mm
■
Balanced flue connection pipe from boiler to shaft,
7
80/125 mm
■
Minimum shaft cross-section
–
Square: 175 x 175 mm
–
Round:
7
195 mm
■
Height between floors min. 2.5 m
■
Max. 6 boilers with the same rated heating output
connected to the flue system
0
1.
Tap
MODE
.
0
2.
/ until
CONFI
flashes.
0
3. OK
to confirm.
"P" appears in the l.h. display area. The r.h. dis-
play area flashes.
0
4.
Use / to select "12".
0
5. OK
to confirm.
"1" flashes in the l.h. display area.
0
6.
Use / to select "4".
0
7. OK
to confirm.
"0" flashes in the r.h. display area.
0
8.
Refer to the following tables for the correction fac-
tor required for the flue system.
0
9.
Use / to set the correction factor.
10. OK
to confirm. The selected value is adopted.
Commissioning, inspection, maintenance
Matching the burner output to the flue system
5697789