Hold down
S
and simultaneously for longer than
2 s.
The display will then show the following:
■
Status: "P" (= controlled stop)
■
Service: Modulation level in %. Here
"100" = 100 % = upper heating output.
"0" = 0 % = lower heating output.
Permissible CO
2
content
Gas type
Heating output
CO
2
content, dry
Natural gas E
Wobbe index Ws
≥
13.5 kWh/m
3
(0 °C; 1013.25 mbar)
Upper heating output (100 %)
9.2
±
0.1 %
Lower heating output (0 %)
8.2
±
0.1 %
Natural gas E
Wobbe index Ws < 13.5 kWh/m
3
(0 °C; 1013.25 mbar)
Upper heating output (100 %)
9.0
±
0.1 %
Lower heating output (0 %)
8.0
±
0.1 %
LPG P
Upper heating output (100 %)
10.9
±
0.1 %
Lower heating output (0 %)
10.0
±
0.1 %
CO
2
test at the upper heating output
A
Fig. 9
1.
Press until the service display has counted up to
"100" (= 100 %).
2.
Check the CO
2
content at the flue pipe.
For permissible CO
2
content, see above table.
Commissioning, inspection, maintenance
Checking the CO
2
content
(cont.)
5816717