Type
SVW
SVPA
Permissible temperature
Heating water flow
110 °C
110 °C
Permissible operating pressure
3 bar (0.3 MPa)
6 bar (0.6 MPa)
Test pressure
4.8 bar (0.48 MPa)
9.6 bar (0.96 MPa)
Note
For connection locations, see from page 8.
1.
Connect all pipework with detachable fittings.
2.
Install the flow line with a rise and fit an air vent
valve at the highest point.
3.
Check all connections for leaks after filling the cyl-
inder.
Cylinder bank connected in series (type SVPA 400 l)
Fig. 20
A
Heating water return 3 (HR3) from the heating cir-
cuits
B
Heating water return 4 (HR4) to the heat generator
C
Heating water flow 1 (HV1) to the heating circuits
D
Heating water flow 2 (HV2) from the heat genera-
tor
E
Air vent valve (EL)
F
Drain outlet (E)
Installation sequence
Making the connections on the heating water side
(cont.)