7.1 Vitocell 100-U, type CVUB/CVUC-A
For DHW heating
in conjunction with boilers and solar collectors
Suitable for the following systems:
■ DHW temperature up to
95 °C
■ Heating water flow temperature up to
160 °C
■ Solar flow temperature up to
110 °C
■ Operating pressure
on the heating water side
up to
10 bar
(1.0 MPa)
■ Operating pressure
on the solar side
up to
10 bar (1.0 MPa)
■ Operating pressure
on the DHW side
up to
10 bar (1.0 MPa)
Specification
Type
CVUB
CVUC-A
Cylinder capacity
l
300
300
DIN registration no.
0266/07-13MC/E
Continuous output, upper indirect coil
For DHW heating from
10 to 45 °C
and a
heating water
flow temperature
of … at the heating water flow rate stated below
90 °C
kW
31
l/h
761
80 °C
kW
26
l/h
638
70 °C
kW
20
l/h
491
60 °C
kW
15
l/h
368
50 °C
kW
11
l/h
270
Continuous output, upper indirect coil
For DHW heating from
10 to 60 °C
and a
heating water
flow temperature
of … at the heating water flow rate stated below
90 °C
kW
23
l/h
395
80 °C
kW
20
l/h
344
70 °C
kW
15
l/h
258
Heating water flow rate
for the stated continuous outputs
m
3
/h
3.0
Draw-off rate
l/min
15
Drawable water volume
Without reheating
Cylinder content heated to 60 °C
Water at t = 60 °C (constant)
l
110
Standby heat loss
Q
ST
at 45 K temperature differential to EN 12897:2006
kWh/24 h
1.52
1.15
Standby capacity V
aux
l
127
Solar capacity V
sol
l
173
Dimensions (incl. thermal insulation)
Length a (
7
)
mm
660
Total width b
mm
840
Height c
mm
1735
Height when tilted
mm
1830
Weight
incl. thermal insulation
kg
179
Total weight in operation
kg
481
Heating water capacity
– Upper indirect coil
l
6
– Lower indirect coil
l
10
Heating surface
– Upper indirect coil
m
2
0.9
– Lower indirect coil
m
2
1.5
Connections
(male thread)
Heating water flow and return
R
1
Cold water, DHW
R
1
DHW circulation
R
1
Energy efficiency class
B
A
Information regarding continuous output of the upper indirect
coil
When engineering systems with the specified or calculated continu-
ous output, select a matching circulation pump. The stated continu-
ous output is only achieved when the rated boiler heating output ≥
continuous output.
Note
The cylinder is also available as Vitocell 100-W, type CVUB in white.
The Vitocell 100-W, type CVUC-A is only available in white.