180
Enabling the compressor stage.
Note
Never block the heat pump compressor
in standard mode.
"Yes"
Compressor stage is used.
"No"
Compressor stage is not
used, e.g. in case of a fault.
Menu
■
"Device settings"
■
"Programming"
■
"Compressor"
■
"Enable"
Delivered condition
Yes
Setting
Yes/No
Heat pump output
Type-dependent heating output of heat pump (for the energy statement) and lag heat
pumps in a cascade.
■
Refrigerant circuit statement
The heat pump control unit calculates
the actual compressor power con-
sumption from the type-dependent
heating output and the internal output
curves.
From the pressures and temperatures
in the refrigerant circuit, the heat pump
control unit calculates the heating out-
put.
The ratio of transferred heating output
to consumed electric current gives the
coefficient of performance (COP).
Both values are calculated and saved
every month. The values of the last 12
months and that of the current month
can be scanned under
"Energy state-
ment"
■
Operating lag heat pumps in cas-
cades
If the type-dependent heating output is
correctly set (see page 172), the heat
pump control unit optimises the stop-
ping and starting of the lag heat
pumps.
Note
Pressing
ª
in menu "Output" or
i
(reset) in the main menu returns
the values to their delivered condition.
Menu
■
"Device settings"
■
"Programming"
■
"Compressor"
■
"Output"
Delivered condition
10 kW
Setting
Range: 1 to
255 kW
Type AWH-I/
AWH-O
110: 10 kW
114: 14 kW
120: 20 kW
Compressor control settings
Enabling the compressor
5414 828 GB
Содержание VITOCAL 350-A
Страница 54: ...54 5 3x 7 6 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Страница 57: ...57 3x 8 9 3x 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB Installation ...
Страница 58: ...58 2x 10 11 3x 3x Installation sequence Fitting the outer panels cont 5414 828 GB ...
Страница 60: ...60 4 mm 4x 4x 4x 3 2 1 2 2 Installation sequence Fitting the silencer hoods only type AWH O 5414 828 GB ...
Страница 62: ...62 Type AWH I 1 Installation sequence Installing the heat pump cont 5414 828 GB ...
Страница 63: ...63 Type AWH O 2 3 4 5 4x 1 Installation sequence Installing the heat pump cont 5414 828 GB Installation ...
Страница 115: ...115 Fitting the front panel 1 2 Installation sequence Closing the heat pump cont 5414 828 GB Installation ...
Страница 227: ...227 053 032 039 034 038 033 034 039 040 027 Parts lists Parts list type AWH I cont 5414 828 GB Service ...
Страница 228: ...228 052 054 059 008 056 025 020 Parts lists Parts list type AWH I cont 5414 828 GB ...
Страница 236: ...236 053 032 039 034 038 033 034 039 027 Parts lists Parts list type AWH O cont 5414 828 GB ...
Страница 237: ...237 052 054 059 008 055 025 020 Parts lists Parts list type AWH O cont 5414 828 GB Service ...