73
External functions
Parameter
Setting
External changeover of the
operating status of various
system components
"System definition"
Ó
"System components for
external changeover
7011"
"0"
to
"127"
"System definition"
Ó
"Operating status for ex-
ternal changeover 7012"
"0"
to
"3"
"System definition"
Ó
"Duration of external
changeover 7013"
"0"
to
"12"
External blocking of compres-
sor and pumps
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
External blocking of the com-
pressor; mixer in control
mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on
heat pump/heating circuits
7015"
"0"
to
"8"
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
Heat pump cascade
Parameter
Setting
Lead heat pump
Lag heat pump
"System definition"
Ó
"System scheme 7000"
"0"
to
"10"
"11"
"Communication"
Ó
"Enable LON communication
module 7710"
"1"
"1"
"System definition"
Ó
"Cascade control 700A"
"2"
"0"
"System definition"
Ó
"Number of lag heat pumps
7029"
"1"
to
"4"
–
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5516 436 GB
Service
Содержание VITOCAL 300-A
Страница 5: ...5 Certificates Declaration of conformity 116 Keyword index 117 Index Index cont 5516 436 GB ...
Страница 79: ...79 8x Troubleshooting Repairs cont 5516 436 GB Service ...
Страница 94: ...94 0011 0010 0009 0008 0004 0005 0006 0007 0001 0003 0002 Parts lists Additional components cont 5516 436 GB ...
Страница 96: ...96 0007 0007 0007 0004 0005 0004 0003 0003 0003 0003 0006 0002 0001 Parts lists Air module cont 5516 436 GB ...
Страница 122: ...122 5516 436 GB ...
Страница 123: ...123 5516 436 GB ...