13
M
Power cable, compressor/fan (3/N/
PE 400 V/50 Hz, on site)
Recommended cable: 5 x 2.5 mm
2
,
flexible
N
2 connecting cables inside DN 100
KG conduit (on site), fully wired (5,
15 or 30 m):
■
Control cable
230 V~
■
LV lead
< 42 V
Note
The maximum cable length is
30 m. Extensions are not permis-
sible.
O
Hydraulic connection lines (heating
water flow and heating water return)
P
Underground channel
Q
Wall duct with expanding mortar (on
site) for hydraulic connection line
R
Moisture-proof and waterproof wall
ducts (on site)
S
Drain & fill facility with shut-off valve
(for draining with compressed air)
T
Expansion vessel with safety
assembly (accessories)
U
Clearance, house wall — founda-
tions:
■ Maximum clearance depends on
length of the connecting cables
and hydraulic connection lines:
Max. 23 m
■ Maintain the minimum clearance
to other objects (> 1.5 m) when
siting.
Heating water connection (hydraulic
connection lines
O
)
Use the hydraulic connection set (acces-
sory). The connection set is fully pre-
pared in different lengths. The flow and
return lines are flexible and have 2 adap-
tors each. The lines are located inside a
common thermal insulation.
■ Flow/return line: 2 x DN 32
■ Adaptor fittings: DN 32 to R 1¼
■ Lines are fed into building
Q
through
a wall duct with expanding mortar (on
site).
■ Provide a drain & fill facility
S
for
heating water flow and return in the
building near an external wall and
0.8 m below ground level.
Note
In buildings at ground level, provide a
thermally insulated duct or enable
draining of the heat pump with com-
pressed air.
Frost protection
If the heat pump control unit and heating
circuit pump are ready for operation, the
frost protection function of the heat pump
control unit is enabled. Drain the system
via the drain & fill facility
S
when the
heat pump is taken out of use or if the
power fails for a long period.
In heat pump systems where a power
failure would not be detected (holiday
home), the heating circuits can be oper-
ated with suitable antifreeze. Ensure that
the system components used are com-
patible with the antifreeze.
Preparing for installation
Siting requirements
(cont.)
5516 436 GB
Installation
Содержание VITOCAL 300-A
Страница 5: ...5 Certificates Declaration of conformity 116 Keyword index 117 Index Index cont 5516 436 GB ...
Страница 79: ...79 8x Troubleshooting Repairs cont 5516 436 GB Service ...
Страница 94: ...94 0011 0010 0009 0008 0004 0005 0006 0007 0001 0003 0002 Parts lists Additional components cont 5516 436 GB ...
Страница 96: ...96 0007 0007 0007 0004 0005 0004 0003 0003 0003 0003 0006 0002 0001 Parts lists Air module cont 5516 436 GB ...
Страница 122: ...122 5516 436 GB ...
Страница 123: ...123 5516 436 GB ...