55
Connection to EA1 extension
Condition:
"Enable Smart Grid 7E80"
must be at
"1"
.
A
[{S
DE
[{{]
0-10V
f-]
A
[{A
DE
[{D
DE
+ -
5 6
3 4
1 2
1 2
E
L1
N
C
B
D
Fig. 48
A
EA1 extension
B
Connection to controller and sensor PCB
C
Floating N/O contact 1: The agreement of the
power supply utility may be required
D
Floating N/O contact 2: The agreement of the
power supply utility may be required
E
Power supply 1/N/PE 230 V/50 Hz
Note
■
If Smart Grid is enabled (
"Enable Smart Grid 7E80"
set to
"1"
), both inputs DE2 and DE3
cannot
be
used for signals "External demand" or "External
blocking".
■
The power-OFF function is integral to Smart Grid.
Therefore do
not
connect the power-OFF signal to
terminals X3.6 and X3.7. Do
not
remove jumper.
Connection to heat pump control unit
Condition:
"Enable Smart Grid 7E80"
must be at
"4"
.
X3.1 X3.1
B
C
D
A
Fig. 49
A
Main PCB
B
Connection X3.1 (L') on the luster terminals
C
Floating contact 1: The agreement of the power
supply utility may be required
D
Floating contact 2: The agreement of the power
supply utility may be required
Note
■
If Smart Grid is connected to the two digital inputs on
main PCB (
"Enable Smart Grid 7E80"
set to
"4"
),
the external hook-up for the heating/cooling circuits
must not be switched on (
"Remote control 2003"
set to
"2"
). Otherwise the Smart Grid will not be
active.
■
The power-OFF function is integral to Smart Grid. In
this case, therefore, the power-OFF signal must
not
be connected to connections X3.6 and X3.7.
Installation sequence
Power supply
(cont.)
5831412
Installation
Содержание Vitocal 222-A
Страница 80: ...80 Fig 64 Maintenance Indoor unit Placing the control unit panel in its service position 5831412 Maintenance...
Страница 92: ...92 Maintenance Checking the fuses cont 5831412 Maintenance...
Страница 102: ...102 0004 0005 0001 0002 0003 0006 0007 Fig 74 Indoor unit parts lists Miscellaneous 5831412 Components...
Страница 104: ...104 Indoor unit parts lists Miscellaneous cont 5831412 Components...
Страница 112: ...112 Outdoor unit parts list 230 V types 221 A04 to A08 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 120: ...120 Outdoor unit parts list 230 V types 221 A10 to A16 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 154: ...154 5831412...
Страница 155: ...155 5831412...