Weight of outdoor units
Vitocal 200-A
Type
Weight in kg
230 V appliances
■
AWOT-M-E
■
AWOT-M-E-AC
221.A04
102
221.A06
102
221.A08
103
221.A10
145
221.A13
145
221.A16
145
400 V appliances
■
AWOT-E
■
AWOT-E-AC
221.A10
153
221.A13
153
221.A16
153
Installation location
■
Select a site with good air circulation, so that the
cooled air can dissipate and be replaced by warm
air.
■
Never install in the corners of rooms, in recesses or
between walls. This could result in an "air short cir-
cuit" between the air being discharged and the air
being drawn in.
!
Please note
An "air short circuit" during
heating mode
will
result in the cooled, discharged air re-entering
the unit. This can result in reduced heat pump
efficiency and defrosting problems.
Avoid "air short circuits".
!
Please note
An "air short circuit" during
cooling mode
will
result in the heated, discharged air re-entering
the unit. This can lead to high pressure faults.
Avoid "air short circuits".
■
If siting the appliance in a location that is exposed to
wind, ensure that the wind cannot influence the fan
area. Strong wind can have a negative influence on
the air flow through the evaporator.
■
Select an installation location where the evaporator
cannot be blocked by leaves, snow, etc.
■
Select the installation location giving due considera-
tion to the physical laws concerning the propagation
and reflection of sound.
Technical guide
■
Never install next to or below bedroom windows.
■
Maintain a clearance of at least 3 m to pathways,
downpipes or sealed surfaces. The cooled air in the
discharge area creates a risk of ice forming when
outside temperatures are below 10 °C.
■
The installation location must be easily accessible,
for example for maintenance work: See "minimum
clearances".
Installation sequence
Installing the outdoor unit
(cont.)
5831412
Installation
Содержание Vitocal 222-A
Страница 80: ...80 Fig 64 Maintenance Indoor unit Placing the control unit panel in its service position 5831412 Maintenance...
Страница 92: ...92 Maintenance Checking the fuses cont 5831412 Maintenance...
Страница 102: ...102 0004 0005 0001 0002 0003 0006 0007 Fig 74 Indoor unit parts lists Miscellaneous 5831412 Components...
Страница 104: ...104 Indoor unit parts lists Miscellaneous cont 5831412 Components...
Страница 112: ...112 Outdoor unit parts list 230 V types 221 A04 to A08 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 120: ...120 Outdoor unit parts list 230 V types 221 A10 to A16 Outdoor unit electrical equipment 230 V cont 5831412 Components...
Страница 154: ...154 5831412...
Страница 155: ...155 5831412...