105
Type AWO-M/AWO-M-E/AWO-M-E-AC
201.A04
201.A06
201.A08
201.A10
201.A13
201.A16
Max. power consumption
Fan
W
45
45
115
2 x 115
2 x 115
2 x 115
Outdoor unit
kW
2.85
3.20
3.30
4.55
5.08
5.08
Secondary pump (PWM)
W
60
60
60
60
60
60
■
Energy efficiency index EEI
≤
0.2
≤
0.2
≤
0.2
≤
0.2
≤
0.2
≤
0.2
Control unit/PCB, outdoor unit
W
15
15
15
15
15
15
Control unit/PCB, indoor unit
W
10
10
10
10
10
10
Control unit/PCB power, indoor
unit
W
1000
1000
1000
1000
1000
1000
Refrigerant circuit
Refrigerant
R410A
R410A
R410A
R410A
R410A
R410A
■
Safety assembly
A1
A1
A1
A1
A1
A1
■
Refrigerant charge
kg
1.40
1.40
1.40
2.40
2.40
2.40
■
Global warming potential
(GWP)
*2
1924
1924
1924
1924
1924
1924
■
CO
2
equivalent
t
2.7
2.7
2.7
4.6
4.6
4.6
Compressor (hermetically
sealed)
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
■
Oil in compressor
Type
3 MAF
POE
3 MAF
POE
3 MAF
POE
3 MAF
POE
3 MAF
POE
3 MAF
POE
■
Quantity of oil in compressor
l
0.76
0.76
0.76
1.17
1.17
1.17
Permissible operating pressure
■
High pressure side
bar
43
43
43
43
43
43
MPa
4.3
4.3
4.3
4.3
4.3
4.3
■
Low pressure side
bar
28
28
28
28
28
28
MPa
2.8
2.8
2.8
2.8
2.8
2.8
Outdoor unit dimensions
Total length
mm
546
546
546
546
546
546
Total width
mm
1109
1109
1109
1109
1109
1109
Total height
mm
753
753
753
1377
1377
1377
Indoor unit dimensions
Total length
mm
370
370
370
370
370
370
Total width
mm
450
450
450
450
450
450
Total height
mm
880
880
880
880
880
880
Total weight
Outdoor unit
kg
102
102
103
145
145
145
Indoor unit
■
Type AWO-M
kg
40
40
40
40
40
40
■
Type AWO-M-E/AWO-M-E-AC kg
41
41
41
41
41
41
Permissible operating pres-
sure
, secondary side
bar
3
3
3
3
3
3
MPa
0.3
0.3
0.3
0.3
0.3
0.3
*2
Based on the Fifth Assessment Report of the Intergovernmental Panel on Climate Change (IPCC)
Specification
Specification
(cont.)
6150148
Appendix