113
Operating states, actuators and sensors can be
checked in the following menus:
■
Under
"Information"
Submenu in the extended
"Standard menu"
.
■
Under
"Diagnosis"
Submenu in the
"Service"
menu.
Note
Check the temperature values or states of the indica-
ted inputs for "function and logic".
Examples of "function and logic":
■
Are the temperature values of the sensors in the nor-
mal range?
■
Is the state of the maintenance cover (open or
closed) correct?
■
Is the state of the light barrier (free or interrupted)
correct?
■
Residual oxygen content OK?
Calling up the "Information" menu
Press the following keys:
1.
å
"Menu"
appears.
2.
|
/
~
for
"Information"
.
3.
d
to confirm.
4.
|
/
~
+
d
for the required information in the
menu.
5.
ä
until the default display is shown.
Calling up the "Diagnosis" menu
Press the following keys:
1.
d
+
å
simultaneously for approx. 4 s.
The
"Service"
menu appears.
2.
|
/
~
for
"Diagnosis"
3.
d
to confirm.
4.
|
/
~
+
d
for the required information in the
menu.
5.
ä
until the default display is shown.
Checking the outputs (actuators)
Danger
Incorrectly connected actuators can cause dam-
age to the system.
During the actuator tests, check the respective
actuator carefully.
Danger
Activated charging devices (feed screw con-
veyor, screw conveyor, etc.) can cause block-
ages in the fuel discharge system during the
actuator test.
Activate charging devices only briefly.
The following displays appear in sequence:
■
"General"
■
"Boiler"
■
"Charging"
■
"Flue gas filter"
■
"Additional boiler"
■
"Heating circuit 1"
■
"Heating circuit 2"
■
"Heating circuit 3"
■
"Heating circuit 4"
■
"DHW"
■
"DHW circulation"
■
"Solar"
The following actuators can be switched "manually"
Depending on boiler size and settings, other actuators
may be available.
"General"
■
"Central fault Open"
■
"Output On"
"Boiler"
■
"Flue gas fan On"
■
"Ignition On"
■
"Prim air damper Open"
■
"Prim air damper Close"
■
"Sec air damper Open"
■
"Sec air damper Close"
■
"Boiler pump On"
Diagnosis and service checks
Checking operating states, actuators and sensors
5679249
Diagnosis