Page 48 of 72
PYROMAT DYN45 - DYN85 Issue 1.0
5726 783
Heating curve
See room unit extended control system.
Thermostat
See room unit extended control system.
6.4.1 Utility water heater
Adjustable parameters
Screen
number
Parameters
Factory setting
34 Operating
mode:
Operating mode selection.
Off
Utility water heating is switched off.
Timer
The utility water heating is controlled in
accordance with a timer program. The boiler
is only heated up during the heating time.
On
The boiler is heated up when there is a
request for heat and when the system
temperature is sufficient.
Manual
The pump is switched on, the valve is not
controlled.
L
Use this setting only for emergency
operation if a fault message is shown on the
display.
1. Inform your heating specialists for further
instructions on fault rectification.
Timer
35
Number of heating periods:
The week program is entered in the form of
heating periods. Each week program comprises
heating days, start and end.
There are a maximum of 7 heating periods
available.
1
36
Heating period 1, heating day:
Day or days for which the switching times are to
be applied. The heating days are selected with
keys F1 (for Monday) to F7 (for Sunday).
One button press
Æ
day selected, one further
button press
Æ
day deselected.
L
This setting is only available in timer
operating mode.
Mon to Sun
37
Heating period 1, start:
Adjust start release of utility water heating.
L
This setting is only available in timer
operating mode.
06:00