PYROMAT DYN45 - DYN85 Issue 1.0
Page 31 of 72
Danger of deflagration!
Low temperature gas can form due to fuel in the firebox during heat-up with automatic fuel
feed.
Caution!
1. Under no circumstances feed fuel into the firebox by hand.
2. Ensure that the firebox is empty.
1. Start heating operation:
Press F2 "PYROMAT auto" button.
L
The loading modules are switched on in the appropriate sequence. If there is
sufficient fuel in the combustion chamber the whole loading system switches off.
L
The automatic ignition starts. The ignition process is stopped as soon as the fire
has caught.
L
In automatic mode the turbolators must be installed in the heat exchanger. With
particularly damp fuel or exhaust gas temperatures below 160°C in heating
operation, the turbolators must be removed. The removal of the turbolators is
described in chapter "Servicing, cleaning", "Clean pipe heat exchanger (4)".