115
Control unit
message
System characteristics
Cause
Measures
F.3
Regulates without return tem-
perature sensor.
Lead break, return tem-
perature sensor
Check return temperature sensor
(see page 140).
F.4
Regulates without return tem-
perature sensor.
Short circuit, return tem-
perature sensor
Check return temperature sensor
(see page 140).
F.5
Flow rate not being moni-
tored.
Lead break, flow sensor
Check plug 33/X6 and cable be-
tween burner control unit and flow
sensor.
Turn the ON/OFF switch off and
back on again.
F.7
No DHW heating
Lead break, cylinder tem-
perature sensor
Check cylinder temperature sensor
(see page 140).
F.8
No DHW heating
Short circuit, cylinder tem-
perature sensor
Check cylinder temperature sensor
(see page 140).
F.9
No DHW heating
Lead break, outlet temper-
ature sensor DHW
Check DHW outlet temperature
sensor (see page 140).
F.10
No DHW heating
Short circuit, outlet tem-
perature sensor DHW
Check DHW outlet temperature
sensor (see page 140).
F.13
Regulates as if the outside
temperature were 0 °C.
Lead break, outside tem-
perature sensor
Check outside cylinder tempera-
ture sensor (see page 140).
F.14
Regulates as if the outside
temperature were 0 °C.
Short circuit, outside tem-
perature sensor
Check outside cylinder tempera-
ture sensor (see page 140).
F.29
Regulates without flow tem-
perature sensor for low loss
header.
Lead break, low loss
header sensor
Check the low loss header sensor.
F.30
Regulates without flow tem-
perature sensor for low loss
header.
Short circuit, low loss
header sensor
Check the low loss header sensor.
F.37
Burner locked out
Internal circulation pump off
No room heating and no
DHW heating
Lead break
system pressure sensor
Check system pressure sensor.
F.38
Burner locked out
Internal circulation pump off
No room heating and no
DHW heating
Short circuit
system pressure sensor
Check system pressure sensor.
F.49
Burner in a fault state
Lead break, flue gas tem-
perature sensor
Check flue gas temperature sensor
(see page 140).
Reset device.
F.50
Burner in a fault state
Short circuit, flue gas tem-
perature sensor
Check flue gas temperature sensor
(see page 140).
Reset device.
F.55
Burner in a fault state
Lead break, CO sensor
Check CO sensor.
Reset device.
F.56
Burner in a fault state
Short circuit, CO sensor
Check CO sensor.
Reset device.
F.57
Control mode without room
influence
Lead break, room temper-
ature sensor
Check external room temperature
sensor of heating circuit or room
temperature sensor of remote con-
trol unit.
Troubleshooting
Fault messages on the gas condensing module/fuel cell module programming unit
5853335
Diagnosis