16
Permissible temperatures
Solar side
160 °C
Heating water side
160 °C
Permissible operating pressure
Solar side
10 bar
(1.0 MPa)
Heating water side
10 bar
(1.0 MPa)
Test pressure
Solar side
16 bar
(1.6 MPa)
Heating water side
16 bar
(1.6 MPa)
Note
Vitosol collectors can be operated with up to 6 bar
(0.6 MPa).
System scheme with solar collectors and boiler
■
Heating of DHW by solar collectors via the
lower
internal indirect coil
■
Heat supply for reheating or heating DHW with a
boiler via the
upper
internal indirect coil
KW
WW
1
2
3
5
6
7
8
9
4
S1
S2
P
M
STB
qP
Fig. 16
KW Cold water
HW DHW
S1 Collector temperature sensor (for version with
SDIO/SM1A electronics module: Insert SDIO/
SM1A plug
&
into electronics module)
S2 Cylinder temperature sensor (on the solar side)
(for version with SDIO/SM1A electronics module:
Insert SDIO/SM1A plug
%
into electronics mod-
ule)
1
Vitocell 100-B or Vitocell 100-W comprising:
2
DHW cylinder
3
Solar-Divicon
4
Vitosolic 100 SDIO/SM1A electronics module
Connecting the heating water side and solar side
(cont.)
5838690