21
Checking all gas connections for tightness
Danger
Escaping gas leads to a risk of explosion.
Always carry out the following steps.
1.
Insert new gaskets in all gas fittings that have been
opened and retighten them.
2.
Open the gas shut-off valve.
3.
Check the inlet joints of the gas train for tightness.
!
Please note
The use of leak detection spray can result in
faulty operation.
Leak detection spray must not come into
contact with electrical contacts.
4.
Start the burner (see page 9).
5.
Check for tightness
■
Outlet joints of the gas train
■
Joint between the fan and the boiler flange
■
Joint between the fan and the Venturi pipe
Checking the rotary damper setting
0
0
Fig. 21
1.
Open the gas shut-off valve.
Commissioning, inspection, maintenance
Checking the filter element in the gas line (if installed) and replacing if
required
5783 337 GB