133
3.
Press reset button
R
and repeat commissioning.
The check is repeated until it is completed suc-
cessfully.
Checking the temperature limiter
If the burner control unit cannot be reset after a fault
shutdown although the boiler water temperature is
below approx. 75 °C, check the following:
A
Fig. 109
1.
Pull leads from temperature limiter
A
.
2.
Check continuity of the temperature limiter with a
multimeter.
3.
Remove faulty temperature limiter.
4.
Coat the new temperature limiter with heat con-
ducting paste and install it.
5.
After commissioning, press reset
R
on the control
unit.