114
2.
On programming unit
B
, select the required dis-
play (
81
to
85
) under
ITEM
using / .
In displays
81
to
85
, the set value and the
response time are shown alternately.
For an explanation of the displays, see the follow-
ing table:
ITEM
Meaning
Set value
Response time
81
Min. voltage
184 V
200 s
82
Max. voltage
253 V
600 s
83
Max. voltage
264.5 V
200 ms
84
Min. frequency
47.5 Hz
200 ms
85
Max. frequency
51.5 Hz
200 ms
Resetting fuel cell module data
The following statistical data from the fuel cell module
can be reset:
■
Power generated
■
CO2 reduction
■
Gas consumption history
Extended menu
1.
2.
"Service"
3.
"Service functions"
4.
"Reset fuel cell data"
Diagnosis and service scans
Fuel cell module
(cont.)
5775 636 GB
Diagnosis
Содержание C3TB
Страница 44: ...44 3 5 1 2x 2 4 7 6 Fig 43 Installation sequence Fitting the front panels 5775 636 GB Installation ...
Страница 48: ...48 14 Fig 47 Installation sequence If required for easier handling Dismantling cont 5775 636 GB Installation ...
Страница 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Страница 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Страница 148: ...148 0001 0001 0003 0003 0002 0002 0004 Fig 118 Parts lists External connection assembly 5775 636 GB Components ...
Страница 154: ...154 0006 0003 0005 0001 0002 0004 Fig 121 Parts lists Miscellaneous assembly 5775 636 GB Components ...
Страница 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Страница 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Страница 187: ...187 5775 636 GB ...