68
Measuring the static pressure and supply pressure
Danger
CO build-up as a result of incor-
rect burner adjustment can have
serious health implications.
A CO test must be performed
before and after work on gas
appliances.
A
1.
Close the gas shut-off valve.
2.
Undo the screw inside test nipple
A
(IN) on the gas train, but never
remove, and connect the pressure
gauge.
3.
Open the gas shut-off valve.
4.
Check the static pressure and record
the value in the report on page 184.
Set value: max. 25 mbar.
5.
Start the boiler.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5618 294 GB