23
!
Please note
Observe the permissible floor
load.
■ Align the appliance horizon-
tally.
If the adjustable feet are used
to compensate for an uneven
floor (max. 10 mm), the pres-
sure load on the feet must be
distributed evenly.
■ The total weight must be con-
sidered (see table).
Total weight
Type
Weight
BW 351.A07
136 kg
BWS 351.A07
132 kg
BWC 351.A07
146 kg
To prevent the transmission of structure-
borne noise, never site the appliance on
ceilings with wooden joists, e.g. in the
attic.
Minimum room volume (to EN 378)
Type
Minimum spa-
tial volume
BW 351.A07
9.4 m
3
BWS 351.A07
9.4 m
3
BWC 351.A07
9.4 m
3
Minimum clearances
Single stage (type BW/BWC)
≥ 400
≥ 1500
A
B
Preparing for installation
Siting requirements
(cont.)
5546 273 GB
Installation