![Viessmann B2TF Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/viessmann/b2tf/b2tf_installation-and-service-instructions-manual_1016831074.webp)
74
5. "Message history"
The following is displayed in the message lists:
■
Date and time of the occurrence of the notifica-
tion
■
Notification number
■
Description of the notification
■
Subscriber number of the component on which
the message has occurred:
PlusBus subscriber components
0
EM-S1 extension (ADIO electronics
module)
1 - 15
EM-M1, EM-MX and EM-P1 extensions
(ADIO electronics module)
17 - 31 EM-EA1 extension (DIO electronics
module)
32 - 47 Cylinder module (electronics module
M2IO)
49 - 63 Vitotrol 200-E
64
SDIO/SM1A electronics module
CAN BUS subscriber components
1
HMU heat management unit
50 BCU burner control unit
58 RF module (TCU 200)
59 HMI programming unit
60 Fan unit
90 Gateway
Low power radio subscriber components
49 - 63 Vitotrol 300-E
6.
■
"Faults"
to call up saved fault messages. For
further details, see the following chapter "Fault
messages".
■
"Service messages"
to call up saved service
messages.
■
"Status"
, to call up the saved status messages.
■
"Warnings"
to call up saved warning messages.
■
"Information"
, to call up saved service informa-
tion.
For messages, see chapter "Further messages".
7.
If you wish to delete messages, tap .
8.
to confirm
Checking outputs (actuator test)
Note
When the actuator test is started, all actuators are ini-
tially disabled and valves moved to their central posi-
tion.
Tap the following buttons:
0
1.
" "
0
2. "Service"
0
3.
Enter password
"viservice"
.
0
4.
Confirm with
.
0
5. "Actuator test"
0
6.
to confirm the security prompt.
Note
If an actuator function is not possible due to the
running process, the function is interrupted. A
message appears.
0
7.
Use / to select the required group. See the
table below.
0
8.
Tap the required actuator function. Several func-
tions can be activated simultaneously.
0
9.
If necessary, tap
to confirm. The functions are
active for 30 s.
10.
Use
to end the Actuator test.