![Viessmann B2TF Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/viessmann/b2tf/b2tf_installation-and-service-instructions-manual_1016831069.webp)
69
1192.0 "Minimum flow temperature limit, heating circuit 1"
Setting
Explanations
Minimum flow temperature limit for the heating circuit
20 °C
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
1192.1 "Maximum flow temperature limit, heating circuit 1"
Setting
Explanations
Maximum flow temperature limit for the heating circuit
74 °C
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
1193.0 "Minimum flow temperature limit, heating circuit 2"
Setting
Explanations
Minimum flow temperature limit for the heating circuit
20 °C
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
1193.1 "Maximum flow temperature limit, heating circuit 2"
Setting
Explanations
Maximum flow temperature limit for the heating circuit
74 °C
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
1194.0 "Minimum flow temperature limit, heating circuit 3"
Setting
Explanations
Minimum flow temperature limit for the heating circuit
20 °C
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
1194.1 "Maximum flow temperature limit, heating circuit 3"
Setting
Explanations
Maximum flow temperature limit for the heating circuit
74 °C
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters