![Viessmann B2TF Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/viessmann/b2tf/b2tf_installation-and-service-instructions-manual_1016831040.webp)
40
Supply pressure (flow pressure)
Measures
For natural gas
For LPG
< 20 mbar (2.0 kPa)
< 50 mbar (5.0 kPa)
Do not start the boiler. Notify the gas supply utility or
LPG supplier.
20 - 25 mbar (2.0 -
2.5 kPa)
50 - 57.5 mbar (5.0 -
5.75 kPa)
Start the boiler.
> 25 mbar (2.5 kPa)
> 57.5 mbar (5.75 kPa)
Install a separate gas pressure governor upstream of
the system. Set the pre-charge pressure to 20 mbar
(2.0 kPa) for natural gas and 50 mbar (5.0 kPa) for
LPG. Notify the gas supply utility or LPG supplier.
Function sequence and possible faults
Display
Measure
Control unit issues a heat
demand
No
Increase set value. Ensure
heat transfer.
Yes
Fan starts
No
Fault F.59, F.457
Check connection cables on
fan. Check power supply on
fan.
Yes
Ignition
No
Fault F.359
Check ignition module (con-
trol voltage 230 V across
plugs "X18.1" and "X18.3" on
the burner control units).
Check the gas supply.
Yes
Gas train opens
No
Fault F.357
Check the gas supply pres-
sure.
Yes
Ionisation current builds
No
Fault F.369, F.380
Check distance of ionisation
electrode on burner gauze
assembly.
Purge the gas line.
Yes
Burner in operation
No
Shuts down below the set
boiler water temperature and
restarts immediately.
Check the flue system for
tightness (flue gas recircula-
tion). Check gas flow pres-
sure.
Commissioning, inspection, maintenance
Checking the static pressure and supply pressure
(cont.)
6151778