32
Danger
CO formation as a result of incorrect burner
adjustment can have serious health implications.
Always carry out a CO test before and after
work on gas appliances.
Operation with LPG
Purge the LPG tank twice when commissioning or
making a replacement. Vent the tank and gas connec-
tion line thoroughly after purging.
A
Fig. 24
1.
Close the gas shut-off valve.
2.
Undo screw
A
inside test connector "PE" on the
gas train, but do not remove it, and connect the
pressure gauge.
3.
Open the gas shut-off valve.
4.
Check the static pressure and record the actual
value in the report on page 136.
Set value: max. 57.5 mbar (5.75 kPa).
5.
Start the boiler.
Note
During commissioning, the boiler can enter a fault
state (fault EE is displayed) because of air in the
gas line. After approx. 5 s, press reset button
R
to
reset the burner.
6.
Check the supply (flow) pressure.
Set value:
■
Natural gas: 20 mbar (2.0 kPa)
■
LPG: 50 mbar (5.0 kPa)
Note
Use a suitable measuring instrument with a resolu-
tion of at least 0.1 mbar (0.01 kPa) to check the
supply pressure.
7.
Record the actual value in the report on page 136.
Implement measures as indicated in the table
below.
8.
Shut down the boiler, close the gas shut-off valve.
Remove the pressure gauge and seal test connec-
tor
A
with screw.
9.
Open the gas shut-off valve and start the appliance.
Danger
Gas escaping from the test connector leads
to a risk of explosion.
Check gas tightness at test connector
A
.
Supply pressure (flow pressure)
Measures
For natural gas
For LPG
Below 17.4 mbar
(1.74 kPa)
Below 42.5 mbar
(4.25 kPa)
Do not commission the boiler. Notify your gas supply
utility or LPG supplier.
17.4 to 25 mbar
(1.74 to 2.5 kPa)
42.5 to 57.5 mbar
(4.25 to 5.75 kPa)
Start the boiler.
Above 25 mbar (2.5 kPa)
Above 57.5 mbar
(5.75 kPa)
Install a separate gas pressure governor upstream of
the system and set the flow pressure to 20 mbar
(2.0 kPa) for natural gas or 50 mbar (5.0 kPa) for LPG.
Notify your gas supply utility or LPG supplier.
Commissioning, inspection, maintenance
Checking the static pressure and supply pressure
5773 216 GB
Содержание B2TA
Страница 12: ...12 2 5 1 4 2x 3 Fig 5 Installing the boiler Removing the front panels 5773 216 GB Installation ...
Страница 13: ...13 1 2 SW17 Fig 6 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation ...
Страница 23: ...23 4 1 5 2 2x 3 Fig 16 Installing the boiler Fitting the front panels 5773 216 GB Installation ...
Страница 101: ...101 Parts lists Overview of assemblies 5773 216 GB Components ...
Страница 107: ...107 Parts lists Hydraulics 5773 216 GB Components ...
Страница 118: ...118 0004 0002 0005 0006 0001 0003 Fig 77 Parts lists Miscellaneous 5773 216 GB Components ...
Страница 142: ...142 5773 216 GB ...
Страница 143: ...143 5773 216 GB ...