20
Fig. 10
1.
Push the supplied drain hose on to the drain con-
nector.
2.
Connect the drain hose with a constant fall and a
pipe vent to the drain network or a neutralising sys-
tem.
Note
Route the onward drain line inside the building as
far as possible.
If the onward drain line is routed outside the build-
ing:
■
Use a min. Ø 30 mm line.
■
Protect the line from frost.
■
Keep the line as short as possible.
!
Please note
The drain hose is used to route away any
hot water discharged from the safety valve.
Lay and secure the drain hose in a way that
prevents any risk of scalding.
Note
Observe local waste water regulations.
Filling the trap with water
Fig. 11
Pour at least 0.3 l of water into the flue gas connection.
!
Please note
During commissioning, flue gas may escape
from the condensate drain.
Always fill the trap with water before commis-
sioning.
Note
If there is a risk of frost, only fill the trap just before
commissioning.
Installation sequence
Condensate connection
6173886
Installation